Liebert GXTTM Connecting the UPS Power cables, Connection of optional remote battery cabinets

Page 21

Connecting the UPS Power cables

Power cables connect to screw terminals on a terminal block that is located behind the rear mounted cable box (see figure). The cables enter the UPS through a Gland Plate attached to the rear of the UPS. The Gland Plate must first be removed and drilled to suit the glands or bushes for the cables used. Ensure that the glands are sized so that they hold the cables securely.

UPS Power Section

To Mains

To Load

To External Battery

 

 

(Optional)

6kVA

10kVA

GXT 6 / 10 kVA Connection Diagram

Connection of optional remote battery cabinets.

Full installation instructions are provided with these cabinets. Safety/EMC certification limits the use of these terminals to Liebert supplied options.

Output connections GXT 6000/10000-X models only

Models whose part number ends with an “X” are fitted with an isolating output transformer. The output of this transformer is referenced to earth at the neutral terminal, remove this earth-neutral link when required by local electrical codes.

19

Image 21
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionBattery Charger RECTIFIER/POWER Factor Correction PFC CircuitBattery InverterControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Normal Mode OPERATION- UPS mode Battery Mode OperationOperating Modes Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Audible Alarm Conditions Troubleshooting GuideProblem Cause Solution Troubleshooting Guide UPS Monitoring UPS Intelligent CommunicationsUPS Intellislot Communications Maintenance Installation Considerations Installation InstructionsInspection LocationAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Connecting the UPS Power cables Connection of optional remote battery cabinetsOutput connections GXT 6000/10000-X models only Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT