Liebert GXTTM user manual Specifications

Page 27

SPECIFICATIONS

MODEL NUMBER

GXT6000T-230

 

GXT10000T-230

MODEL RATING VA/W (max)

6000 / 4200

 

10000 / 7000

DIMENSIONS: mm (in)

 

 

 

Unit

260 x 555 x 803

 

340 x 650 x 960

W x D x H

(10.5 x 22.0 x 31.5)

 

(13.5 x 25.5 x 38.0)

Shipping

400 x 850 x 1065

 

510 x 840 x 1235

 

 

W x D x H

(16.0 x 33.5 x 42.0)

 

(20.0 x 33.0 x 48.5)

 

 

WEIGHT: kg (lbs)

 

 

 

Unit

99 (218)

 

187 (412)

Shipping

130 (288)

 

227 (500)

Input/Output Connections

Hardwire terminal block

INPUT AC PARAMETERS

 

 

 

Voltage Range (typical)

230 VAC nominal; variable based upon output load

100% - 90% Loading

186 VAC to 280 VAC; ±5.0 VAC

90% - 70% Loading

159 VAC to 280 VAC; ±5.0 VAC

70% - 30% Loading

139 VAC to 280 VAC; ±5.0 VAC

30% - 0% Loading

119 VAC to 280 VAC; ±5.0 VAC

Frequency

46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing

OUTPUT AC PARAMETERS

 

 

 

Voltage

208/220/230/240 VAC (switch selectable); ±3%

Frequency

50 Hz or 60 Hz; auto sensing

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to

 

 

bypass

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, nonspillable, lead acid

Qty. x Voltage x Rating

20 x 12V x 7.0 Ah

 

40 x 12V x 7.0 Ah

Back-up Time

7 min. minimum

 

10 min. minimum

Recharge Time

7 hours to 95% capacity after full discharge into 100%

(Internal Batteries Only)

 

load

 

 

 

ENVIROMENTAL

 

 

 

Operating Temperature

0° C to +40° C (+32° F to +104° F)

Storage Temperature

-15° C to +50° C (+5° F to +122 °F)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000 m (10,000 ft.) at 40° C without derating

Storage Elevation

15.000 m (50,000 ft.) maximum

Audible Noise

<55 dB ”A” at 1 metre

 

<65 dB ”A” at 1 metre

AGENCY

 

 

 

Safety

EN50091-1-1; TUV/GS Listed; CE Low Voltage Directive

EMI/EMC

EN50091-2, Class A; CE EMC Directive

Immunity

IEC 801-2, Level 4 / IEC 801-3,

 

Level 3 / IEC 801-4, Level 4 / IEC801-5,Level 3

25

Image 27
Contents UPStation GXT Important Safety Instructions Glossary of Symbols Major Components Introduction and System DescriptionInverter RECTIFIER/POWER Factor Correction PFC CircuitBattery Charger BatteryControls and Indicators Output OFF/BYPASS Button UPS ON/Alarm Silence/Manual Battery Test ButtonGXT 6 & 10 kVA Normal Mode OPERATION- UPS mode Battery Mode OperationOperating Modes Bypass Mode Operation Starting the UPS Powering Down the UPSOperation in Battery Mode Troubleshooting Audible Alarm Conditions Troubleshooting GuideProblem Cause Solution Troubleshooting Guide UPS Monitoring UPS Intelligent CommunicationsUPS Intellislot Communications Maintenance Location Installation InstructionsInstallation Considerations InspectionAirflow Dissipation Output Input Current Rating Electrical Installation ConsiderationsElectrical Connections Connecting the UPS Power cables Connection of optional remote battery cabinetsOutput connections GXT 6000/10000-X models only Stabilisers/Levelling Feet UPS Remote shutdown option PIN Assignment Collector to EmitterSerial Communications Ferrite Bead InstallationCommissioning the UPS Output Voltage Selector SwitchesBattery Run Times Specifications GXT6000T-230X GXT10000T-230X Life Support Applications Limited WarrantyTechnical Support UPStation GXT