GarrettCom 6K8 manual C5.0 Installation, C5.1 UL Requirements

Page 68

Magnum 6K8-Series Industrial Field Switch

Installation and User Guide 03/06)

because of the blocking action of the diodes. This is true even if one input connection is reversed while the Switch is operating from the other source.

e)The Switch will not receive power (and will not work) when both inputs are simultaneously absent or are both incorrectly connected.

C5.0 INSTALLATION

This section describes the proper connection of the -48VDC, 24VDC and 125VDC dual source leads to the -48VDC, 24VDC &

125VDC power terminal block on the Magnum 6Ks Switch

as shown in Fig.

 

The -48VDC terminal block on the Magnum 6K8-Series

Switch, as shown in Fig C5.0 is

 

DC Terminal

located on the left front of the unit

Block (Dual-Source)

and is equipped with five (5)

 

 

screw-down lead posts.

The primary terminals are identified as positive (A+),

negative (A-), and the secondary power terminals as negative (B-), positive(B+). The chassis “earth” or ground (GND) is a threaded post with a #6 nut. The Dual Source terminal block for the 24VDC and 125VDC are similar. Figure C5.0: -48VDC-Dual-

Src, wiring connections to the External Terminal Block on a Magnum 6K8 -48VDC

Note: The GND should be hooked up first. The 6K8-Series unit has a floating ground, so the user may elect to Ground either + or = terminal to suit the customer’s use. Before connecting hot lines to the Terminal Block of –48VDC, 24VDC or 125VDC, always use a digital voltmeter to measure the output voltage of the power supply and determine the lead which is more “+ve potential”. The more “+ve” voltage lead from 48V or –48V supply must be connected to the post labeled “+”.

The connection procedure is straightforward. Simply connect the DC leads to the Switch’s power terminals, positive (+) and negative (-) screws. The use of Ground (GND) is optional; it connects to the Switch chassis. Ensure that each lead is securely tightened.

The 24VDC & 125VDC terminal block on Magnum 6K8-Series’s is similar to that described in the –48VDC information above.

C5.1 UL Requirements

The following must be adhered to in order to conform to UL requirements:

1.Minimum 18 AWG cable for connection to a Centralized DC power source.

2.Minimum 14 AWG cable for connection to earthing wiring.

3.Use only with Listed 10 A circuit breaker provided in building installation.

4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.

5.Fastening torque of the lugs on the terminal block: 9 inch pound max. www . GarrettCom . com

63

Image 68
Contents Industrial Field Switch Trademarks Contacting GarrettCom, Inc Canadian EmissionIntroduction Table of ContentsInstallation Troubleshooting Overview Repeater Port Modules RPMs, 6 types for Ethernet mediaTechnical Specifications PerformanceNetwork Standards and Compliance, hardware Maximum 10 Mbps Ethernet Segment LengthsFiber Single-mode connector types Alarm Relay ContactsManagement Console connector Power Supply InternalDC Power Supply Options Per-port MDI or Mdix on RJ-45Mountings Agency Approvals Magnum 6K8Magnum 6K8 Port Modules Configuration OptionsOrdering Information GBIC1000Mb Transceiver options for Mangum 6K8-Series Introduction Inspecting the Package and Product Product Description Magnum 6K8-Series 6K8 1a Magnum 6K8-Series, Industrial Field Switch Www . GarrettCom . com Eight-port SFF fiber modules 6K8-MTRJ, 6K8-MLC, 100Mb Fiber Eight-Port Copper Module, 6K8-RJ45 Six-Port 4 + 2Combo Modules, 4@ 10/100 RJ-45 and 2@100MbFiber4@RJ-45 + 2@ 100Mb ST or SCFour-Port 10 Mb and 100Mb mm Fiber ST Modules Gigabit 1000Mbps port modules Packet Prioritization, 802.1p QOSFrame Buffering and Flow Control Managed Network Software MNS-6K for Magnum 6K8-Series „ Managed switching for high performance Ethernet LANs „ Large selection of built-in fiber options at 10/100/1000MbApplications Magnum 6K25 Control Center Scada Locating Magnum 6K8-Series Switches Mounting InstructionsConnecting Ethernet Media Connecting Fiber Optic ST-type, twist-lockIeee Standard Media Type Max. Distance Port Module Fiber CopperMedia Ieee Standard Connecting Fiber Optic SC-type, Snap-InConnecting Single-Mode Fiber Optic Twisted Pair CAT 5E 1000BASE-T RJ-45 Www . GarrettCom . com Quantity Description Installing DIN-RAIL variable brackets on Magnum 6K8Din-Rail kit Installation procedures Www . GarrettCom . com Mounting Dimensions for 6K8 with metal brackets Powering the Magnum 6K8-Series Industrial Field Switch 6K8-Series Port Module 6KPMV Installation Preparation for Installing and Removing 6KPMVs from 6K8’s StopDaughter board Power LED, Pin J5 Power Supply, Pin Dssv Installing 6KPM Cards in the Magnum 6K8-Series 2a a Magnum 6K8 unit with main boardmotherboard onlyFemale latch connector 2b Granddaughter Board shown separately6KPMV Cards into a Magnum 6K8-Series Securely latching up Www . GarrettCom . com Connecting a Management Console Terminal to Magnum 6K8 Retaining screws shown by arrows Remove 6KPM CardRemoving a 6KPM Card Enlarged view of Magnum 6K8-Series Console Port areaDB-9 Console port connector 1 RS-232 DB-9 Console Com port Serial port pin assignmentsAddress Learning Switching FunctionalityFiltering and Forwarding Dual LEDs Status on TOP and Front of the 6K8-Series unit Auto-CrossMDIX and Auto-negotiation, for RJ-45 portsOn with port activity for 10 Mbps and 100Mbps operation OFF for half duplexWww . GarrettCom . com Flow-control, Ieee 802.3x Standard 6KP4V ’cvrIntroduction Magnum 6K8 Industrial Field Switch Port Modules 6KPMV Module DescriptionDual-mode ST-type connectors 6KP4-F10ST, 4@10Mb multi-mode FX-ST twist lock Module Connector Www . GarrettCom . com 5 6KP8-MTRJ, 8 @100Mb multi-mode FX , Mtrj Small-Form-factor Port@ 100Mbps Multi-Mode Fiber portMtrj type ports. The small size Mtrj connectors provides an Magnum 6KP8-45MTModule is a combo module with Copper and fiber Small Form Factor9 6KP8-RJ45 Twisted Pair, 10/100Mb 8-Port 45-2MT eight port Module is a GBIC-SXSC Gigabit fiber1000Mb, multi-mode SC Connector 11a GBIC-LXSC Gigabit fiber 1000Mb, multi-mode SC Connector @ 1000Mb Fiber SC + 2@ 100Mb SCBefore Calling for Assistance No Problem Found When Calling for AssistanceReturn Material Authorization RMA Procedure Appendix B Internal DC Power Supply Options Shipping and Packaging InformationB2.0 -48VDC, 24VDC and 125VDC POWER, Theory of Operation B3.0B4.0 6K8-SERIES, -48V, 24, 125 or 5VDC Installation B4.1 UL Requirements for DC-powered units B5.0 OperationC3.0 DUAL-SOURCE OPTION, Theory of Operation C5.0 Installation C5.1 UL RequirementsC6.0 Ordering Information Optional Example Magnum 6K8 -24VDC