GE GEK-106465A instruction manual Operand Description, SUPCOIL2

Page 21

HARDWARE

3.4.2. BOARD OPTION 2

Option 2 I/O board includes two groups of 4 inputs with one common, in terminals 9 to 10. It also includes 6 auxiliary outputs, in terminals 19 to 30 with normally open contacts and two current sensing (latching) outputs.

Besides, there are 2 groups of inputs for trip circuit supervision. The first group includes two isolated digital inputs, terminals 1-2 and 3-4. The second group, symmetrical and identical to the first, is formed by isolated voltage inputs 15-16 and 17-18.

Inputs in both groups are wet contacts, this means they need to receive a positive in the terminal labeled as + coming from a power supply whose negative is connected to the terminal labelled as -.

Using voltage detectors and current sensing, it is possible to implement several trip or close circuit supervision schemes, as well as protection of the unit output contact.

In order to implement these schemes, it is not necessary to perform any setting in the unit. Internal functions are always operative and provide the following logic operands:

OPERAND

 

DESCRIPTION

CONTACT

INPUT_00_08

Active when voltage is detected in terminals 1 - 2 (circuit 1)

(Va_COIL1)

 

 

CONTACT

INPUT_00_09

Active when voltage is detected in terminals 3 - 4 (circuit 1)

(Vb_COIL1)

 

 

CONTACT

INPUT_00_10

Active when voltage is detected in terminals 15 - 16 (circuit 2)

(Va_COIL2)

 

 

CONTACT

INPUT_00_11

Active when voltage is detected in terminals 17 - 18 (circuit 2)

(Vb_COIL1)

 

 

CONTACT

INPUT_00_12

Active if current is detected by sensor in output O7 (F31-F33)

(O7_SEAL)

 

 

CONTACT

INPUT_00_13

Active if current is detected by sensor in output O8 (F34-F36)

(O8_SEAL)

 

 

CONTACT

INPUT_00_14

Active when continuity is detected in circuit 1

(SUP_COIL1)

 

 

CONTACT

INPUT_00_15

Active when continuity is detected in circuit 2

(SUP_COIL2)

 

 

A continuity failure is detected in a circuit when both voltage detectors (Va and Vb) detect lack of voltage during more than 500 ms. This function is not influenced by the breaker status.

These operands can be associated to internal signals (virtual outputs), LEDs or unit outputs, to issue alarm signals or to block elements, for example for blocking the Breaker close if an abnormality is detected in the trip circuit.

Available schemes are as follows:

1.Without supervision

2.With current supervision (with seal-in)

3.With simple voltage supervision

4.With double voltage supervision

5.With current and simple voltage supervision (with seal-in)

6.With current and double voltage supervision (with seal-in)

20

CIO Remote CAN Digital I/O Module

GEK-106465A

Image 21
Contents CIO Table of Contents Circuit Continuity Supervision Inputs INPUT/OUTPUT Modules DescriptionCIO Front View Important ProceduresIdentification Label A4454P5 Inspection ChecklistAMERICA, Asia and Australia GE Multilin EUROPE, Middle East and Africa GE MultilinSafety Instructions Introduction to F650 and F600 Family of Relays OverviewHardware Architecture Software ArchitectureCommunications Architecture Product Description Summary of FeaturesCIO Description Ordering CodeTechnical Specifications Type Tests Packaging and WeightCategory Standard Class Test ApprovalsModule Description Power supply Input/Output moduleMounting Mechanical DescriptionRear Panel Mounting Rear Cover Description External Connections WiringWiring Diagram for Model CIOH1J1 226B5113F2 Board Option BoardsMixed Termina Inputs Supervision OutputsSUPCOIL2 Operand DescriptionWithout Supervision With Current Supervision with SEAL-IN With Simple Voltage Supervision Circuit Output Breaker Operand Status Internal StateHardware Hardware With Double Voltage Supervision 52/a 52/b Status of Involved Elements Inputs to F650Operand Contact INPUT0015 SUPCOIL2 Software Front IndicatorsUser Interfaces Circuit Supervision and Contact SEAL-IN Circuits Circuit SupervisionContact SEAL-IN INPUT/OUTPUT Boards Settings Control Settings for INPUTS/OUTPUTSGeneral Board Settings Input Logic Settings relative to InputsOutput Logic Settings relative to OutputsINPUTS/OUTPUTS Status Input activation signals Contact InputsInput Status Mixed Board Supervision Board Board F, G, H, J TypeContact Output Activation Signals Contact Output Operates Contact Outputs activation signalsContact Output Status Board F, G, H, JContact Output Resets Contact Output Reset Signals Contact Output ResetsIO Board Status Board StatusVisual Inspection General Considerations on the Power Supply NetworkPower Suply Testing IndicatorsIsolation Tests Source OptionCommunication with the Master Unit Settings/Control Elements/Inputs Outputs/BoardInputs and Outputs Digital InputsCircuit Continuity Supervision Inputs Contact OutputsCoil Latching Circuits