GE GEK-106465A instruction manual 52/a 52/b, Status of Involved Elements Inputs to F650

Page 29

HARDWARE

INTERNAL STATE

V 52/a

V 52/b

SUPERVISION

52 open

ON

ON

OK

52 closed

ON

OFF

OK

TRIP

OFF

OFF

Ok if t < 0.5 s

TRIP with 52 open

OFF

ON

OK

Status of Involved Elements

Inputs to F650

 

CIRCUIT

OUTPUT

BREAKER

OPERAND

 

OPERAND

 

STATUS

STATUS

STATUS

CONTACT

 

CONTACT

 

 

(F35-F36)

 

INPUT_00_10

 

INPUT_00_11

 

 

 

 

(Va_COIL2)

 

(Vb_COIL2)

 

 

 

 

V 52/a (15-16)

 

V 52/b (17-18)

 

Healthy

Open

52 closed

ON

 

OFF

 

Healthy

Open

52 open

ON

 

ON

 

Healthy

Closed

52 closed

OFF

 

OFF

 

 

 

 

 

 

 

 

Healthy

Closed

52 open

OFF

 

ON

 

 

 

 

 

 

 

 

Defective

Open

52 closed

OFF

 

OFF

 

Defective

Open

52 open

OFF

 

OFF

 

Defective

Closed

52 closed

OFF

 

OFF

 

 

 

 

 

 

 

 

Defective

Closed

52 open

OFF

 

OFF

 

Decision

OPERAND CONTACT INPUT_00_15 (SUP_COIL2)

ON

ON

ON (if t < 500 ms) OFF (if t > 500 ms)

ON (if t < 500 ms) OFF (if t > 500 ms)

OFF (500 ms delay)

OFF (500 ms delay)

OFF (500 ms delay)

OFF (500 ms delay)

There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary contact 52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is shown on FIGURE 3-12.

The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs 15- 16 and 17-18.

The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through contact 52/b, (that is closed when the breaker is open).

We must point out that in this scheme, the tripping contact, shown in the example as the CIO trip relay, can be the one in the relay (terminals 35 and 36), or be provided by another protection or by the parallel of several protections. This provides high flexibility in the use of this circuit.

The battery voltage can also be monitored, by using one of the standard digital inputs.

28

CIO Remote CAN Digital I/O Module

GEK-106465A

Image 29 Contents
CIO Table of Contents Circuit Continuity Supervision Inputs INPUT/OUTPUT Modules DescriptionCIO Front View Important ProceduresIdentification Label A4454P5 Inspection ChecklistAMERICA, Asia and Australia GE Multilin EUROPE, Middle East and Africa GE MultilinSafety Instructions Introduction to F650 and F600 Family of Relays OverviewHardware Architecture Software ArchitectureCommunications Architecture Product Description Summary of FeaturesCIO Description Ordering CodeTechnical Specifications Type Tests Packaging and WeightCategory Standard Class Test ApprovalsModule Description Power supply Input/Output moduleMounting Mechanical DescriptionRear Panel Mounting Rear Cover Description External Connections WiringWiring Diagram for Model CIOH1J1 226B5113F2 Board Option BoardsMixed Termina Inputs Supervision OutputsSUPCOIL2 Operand DescriptionWithout Supervision With Current Supervision with SEAL-IN With Simple Voltage Supervision Circuit Output Breaker Operand Status Internal State Hardware Hardware With Double Voltage Supervision Operand Contact INPUT0015 SUPCOIL2 52/a 52/bStatus of Involved Elements Inputs to F650 Software Front IndicatorsUser Interfaces Contact SEAL-IN Circuit Supervision and Contact SEAL-IN CircuitsCircuit Supervision INPUT/OUTPUT Boards Settings Control Settings for INPUTS/OUTPUTSGeneral Board Settings Input Logic Settings relative to InputsOutput Logic Settings relative to OutputsINPUTS/OUTPUTS Status Input activation signals Contact InputsInput Status Mixed Board Supervision Board Board F, G, H, J TypeContact Output Activation Signals Contact Output Operates Contact Outputs activation signalsContact Output Status Board F, G, H, JContact Output Resets Contact Output Reset Signals Contact Output ResetsIO Board Status Board StatusVisual Inspection General Considerations on the Power Supply NetworkPower Suply Testing IndicatorsIsolation Tests Source OptionCommunication with the Master Unit Settings/Control Elements/Inputs Outputs/BoardInputs and Outputs Digital InputsCircuit Continuity Supervision Inputs Contact OutputsCoil Latching Circuits