HARDWARE

The following lines describe the different types of connection to create each scheme in an easy way. As the supervision circuits are identical, we will describe connection examples for the first group. They are also applicable to the second group.

The symmetrical location of digital inputs is an optimization for ensuring a high isolation between groups that, belonging to different groups could be connected to separate batteries, and therefore a greater distance between circuits is required.

3.4.2.1. WITHOUT SUPERVISION

This is a very frequent case, and we must only wire the tripping circuit to terminals 35 and 36, leaving unused terminals 34, 15, 16, 17, 18.

FIGURE 3-8 CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1)

GEK-106465A

CIO Remote CAN Digital I/O Module

21

Image 22
Contents CIO Table of Contents INPUT/OUTPUT Modules Description Circuit Continuity Supervision InputsImportant Procedures CIO Front ViewInspection Checklist Identification Label A4454P5EUROPE, Middle East and Africa GE Multilin AMERICA, Asia and Australia GE MultilinSafety Instructions Hardware Architecture OverviewIntroduction to F650 and F600 Family of Relays Software ArchitectureCommunications Architecture Summary of Features Product DescriptionOrdering Code CIO DescriptionTechnical Specifications Category Standard Class Test Packaging and WeightType Tests ApprovalsPower supply Input/Output module Module DescriptionMechanical Description MountingRear Panel Mounting Rear Cover Description Wiring External ConnectionsWiring Diagram for Model CIOH1J1 226B5113F2 Mixed Termina Inputs Supervision BoardsBoard Option OutputsOperand Description SUPCOIL2Without Supervision With Current Supervision with SEAL-IN With Simple Voltage Supervision Internal State Circuit Output Breaker Operand StatusHardware Hardware With Double Voltage Supervision Status of Involved Elements Inputs to F650 52/a 52/bOperand Contact INPUT0015 SUPCOIL2 Front Indicators SoftwareUser Interfaces Circuit Supervision Circuit Supervision and Contact SEAL-IN CircuitsContact SEAL-IN Control Settings for INPUTS/OUTPUTS INPUT/OUTPUT Boards SettingsGeneral Board Settings Settings relative to Inputs Input LogicSettings relative to Outputs Output LogicInput Status Mixed Board Supervision Board Input activation signals Contact InputsINPUTS/OUTPUTS Status Board F, G, H, J TypeContact Output Status Contact Outputs activation signalsContact Output Activation Signals Contact Output Operates Board F, G, H, JIO Board Status Contact Output Reset Signals Contact Output ResetsContact Output Resets Board StatusGeneral Considerations on the Power Supply Network Visual InspectionIsolation Tests IndicatorsPower Suply Testing Source OptionInputs and Outputs Settings/Control Elements/Inputs Outputs/BoardCommunication with the Master Unit Digital InputsCoil Contact OutputsCircuit Continuity Supervision Inputs Latching Circuits