Settings relative to Inputs:

Input Activation Voltage Threshold: This value can be from 0 to 255 volts. There is a single setting for all inputs in the same group (inputs sharing the same common). In mixed and supervision boards there are two groups of inputs, called A and B.

Debounce Time: This is the debounce time set for inputs (1 to 50 ms). The debounce time is the time window for input filtering. If an input suffers a change of level that lasts less than this set time, the change will not be considered. There is a single setting for all inputs in the same group.

Delay Input Time: This is the delay applied to the input signal; the default value is zero, meaning no delay; the setting range is 0 to 60000 milliseconds (1 minute). This setting is used in slow switchgear applications.

This is not a grouped setting; there is a different setting for each input. It is important not to confuse this delay input time with the debounce time used for filtering undesired transients in the input signal. The Debounce time is always added to the delay input time.

Input Type: Type of logic associated to the physical input. Possible settings are, positive and negative.

Positive and Negative settings correspond to signals that are activated or deactivated with the input level, considering the delay setting. Positive-edge, and Negative-edge settings correspond to signals that are activated with the change of the input signal; in this case, the Delay Input Time will not be considered, only the Debounce Time; this edge signals are deactivated automatically after one PLC scan cycle. FIGURE 5-2 shows the types of signals associated to the different input configuration types.

FIGURE 5-2. INPUT LOGIC

34

CIO Remote CAN Digital I/O Module

GEK-106465A

Image 35 Contents
CIO Table of Contents Circuit Continuity Supervision Inputs INPUT/OUTPUT Modules DescriptionCIO Front View Important ProceduresIdentification Label A4454P5 Inspection ChecklistAMERICA, Asia and Australia GE Multilin EUROPE, Middle East and Africa GE MultilinSafety Instructions Software Architecture OverviewIntroduction to F650 and F600 Family of Relays Hardware ArchitectureCommunications Architecture Product Description Summary of FeaturesCIO Description Ordering CodeTechnical Specifications Approvals Packaging and WeightType Tests Category Standard Class TestModule Description Power supply Input/Output moduleMounting Mechanical DescriptionRear Panel Mounting Rear Cover Description External Connections WiringWiring Diagram for Model CIOH1J1 226B5113F2 Outputs BoardsBoard Option Mixed Termina Inputs SupervisionSUPCOIL2 Operand DescriptionWithout Supervision With Current Supervision with SEAL-IN With Simple Voltage Supervision Circuit Output Breaker Operand Status Internal StateHardware Hardware With Double Voltage Supervision Operand Contact INPUT0015 SUPCOIL2 52/a 52/bStatus of Involved Elements Inputs to F650 Software Front IndicatorsUser Interfaces Contact SEAL-IN Circuit Supervision and Contact SEAL-IN Circuits Circuit Supervision INPUT/OUTPUT Boards Settings Control Settings for INPUTS/OUTPUTSGeneral Board Settings Input Logic Settings relative to InputsOutput Logic Settings relative to OutputsBoard F, G, H, J Type Input activation signals Contact InputsINPUTS/OUTPUTS Status Input Status Mixed Board Supervision BoardBoard F, G, H, J Contact Outputs activation signalsContact Output Activation Signals Contact Output Operates Contact Output StatusBoard Status Contact Output Reset Signals Contact Output ResetsContact Output Resets IO Board StatusVisual Inspection General Considerations on the Power Supply NetworkSource Option IndicatorsPower Suply Testing Isolation TestsDigital Inputs Settings/Control Elements/Inputs Outputs/BoardCommunication with the Master Unit Inputs and OutputsLatching Circuits Contact OutputsCircuit Continuity Supervision Inputs Coil