3.4.2.2. WITH CURRENT SUPERVISION (WITH SEAL-IN)
In this case, as shown on FIGURE
With this scheme, in the case of a failure to open from the breaker auxiliary contact, the CIO output relay will not be the one to open the tripping coil current, as in this case the contact may result damaged, as it is prepared for opening currents around 0.5 A at 125 Vdc.
This latching or memory function is only guaranteed while the unit is powered.
FIGURE 3-9 CURRENT SUPERVISION OF THE TRIPPING CONTACT (A6631F2)