GE GEK-106465A Contact Outputs, Circuit Continuity Supervision Inputs, Coil, Latching Circuits

Page 43

ACCEPTANCE TESTS

The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common. For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4 inputs, the setting is Voltage Threshold B.

Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.

6.7.2. CONTACT OUTPUTS

The correct activation of every output will be verified.

For every output, activation command of a single contact must be given, and then verify that only that contact is activated (Setpoint/Force IO)

For switched contacts, the change of state of both contacts shall be verified.

6.7.3. CIRCUIT CONTINUITY SUPERVISION INPUTS

Supervision inputs will be tested as normal inputs, revising the voltage level, which will be 19 Volts.

Coil 1:

Apply 19 Vdc to both 52/a and 52/b ”Coil 1” circuit supervision inputs and verify that they are activated. Apply -19 Vdc to both 52/a and 52/b ”Coil 1” circuit supervision inputs and verify that they are activated. Remove voltage from both inputs and verify that it takes them 500 ms to change state (deactivate).

Coil 2:

Apply 19 Vdc to both 52/a and 52/b ”Coil 2” circuit supervision inputs and verify that they are activated. Apply -19 Vdc to both 52/a and 52/b ”Coil 2” circuit supervision inputs and verify that they are activated. Remove voltage from both inputs and verify that it takes them 500 ms to change state (deactivate).

6.7.4. LATCHING CIRCUITS

Send a closing command to the latched contact.

Make circulate a current of 200 mA through the contact in series with the sensing terminal. Send an opening command and verify that the contact does not open.

Interrupt current and check than the contact is released.

200

I

Repeat the test for the other latched contact

42

CIO Remote CAN Digital I/O Module

GEK-106465A

Image 43
Contents CIO Table of Contents Circuit Continuity Supervision Inputs INPUT/OUTPUT Modules DescriptionCIO Front View Important ProceduresIdentification Label A4454P5 Inspection ChecklistAMERICA, Asia and Australia GE Multilin EUROPE, Middle East and Africa GE MultilinSafety Instructions Software Architecture OverviewIntroduction to F650 and F600 Family of Relays Hardware ArchitectureCommunications Architecture Product Description Summary of FeaturesCIO Description Ordering CodeTechnical Specifications Approvals Packaging and WeightType Tests Category Standard Class TestModule Description Power supply Input/Output moduleMounting Mechanical DescriptionRear Panel Mounting Rear Cover Description External Connections WiringWiring Diagram for Model CIOH1J1 226B5113F2 Outputs BoardsBoard Option Mixed Termina Inputs SupervisionSUPCOIL2 Operand DescriptionWithout Supervision With Current Supervision with SEAL-IN With Simple Voltage Supervision Circuit Output Breaker Operand Status Internal StateHardware Hardware With Double Voltage Supervision Status of Involved Elements Inputs to F650 52/a 52/bOperand Contact INPUT0015 SUPCOIL2 Software Front IndicatorsUser Interfaces Circuit Supervision Circuit Supervision and Contact SEAL-IN CircuitsContact SEAL-IN INPUT/OUTPUT Boards Settings Control Settings for INPUTS/OUTPUTSGeneral Board Settings Input Logic Settings relative to InputsOutput Logic Settings relative to OutputsBoard F, G, H, J Type Input activation signals Contact InputsINPUTS/OUTPUTS Status Input Status Mixed Board Supervision BoardBoard F, G, H, J Contact Outputs activation signalsContact Output Activation Signals Contact Output Operates Contact Output StatusBoard Status Contact Output Reset Signals Contact Output ResetsContact Output Resets IO Board StatusVisual Inspection General Considerations on the Power Supply NetworkSource Option IndicatorsPower Suply Testing Isolation TestsDigital Inputs Settings/Control Elements/Inputs Outputs/BoardCommunication with the Master Unit Inputs and OutputsLatching Circuits Contact OutputsCircuit Continuity Supervision Inputs Coil