Chapter 3. Installing the CS7000 Controller

Meeting the AC Input Power Requirements

For proper operation, the controller must be connected to a stable power source. The supply source should be capable of delivering at least 1.5 kVA per channel at 220V for 177 Series tools. For the 277 Series tools, at least 2KVA per channel is recommended.

The voltage tolerance for 220V controllers is 208 to 250 VAC.

NOTE:

?

CAUTION!

i

The maximum no-load speed of a nutrunner is based on a nominal AC input voltage of 220V depending on the type of controller; if the actual input voltage is lower, the maximum no load speed of the nutrunner will be lower than specified.

Failure to provide the proper power source can cause the following problems in your CS7000 Fastening System:

The nutrunner might shut down before it reaches the target torque during a rundown cycle.

The nutrunner might not operate when a cycle-on signal is applied to the system.

The maximum free speed of the nutrunner might be lower than specified.

Input Power Protection

A circuit breaker or fuses positioned between the AC input and the servo amplifier provides the controller with short circuit protection.

____________________________________________________________________________________________

December 2005

Page 3-3

Image 33
Contents With Ethernet/CCM Information Hardware Overview ManualHour Technical Support Limited Warranty Please Read This Tool LabelController Label How to Use This Manual PrefaceWho Should Use This Manual Appears in a box in italicized boldface type ConventionsIeee AbbreviationsThis page is left blank intentionally Contents Tool Connector 26 pin Metal SMC Front View Tables FiguresThis page is left blank intentionally General Machine Safety Think Safety First6159939130 CS7000 Controller Hardware Overview Manual Electrical Safety This page is left blank intentionally Identifying the Components Front Panel Latch Parameter Select SwitchRotary Actuator LED DisplayBottom Panel Top PanelInput AC Power Tool ConnectorPrinter/Barcode Connector RS-232 Connector VS SetupEnclosure Interior ConnectorIdentifying the Components Front View of the TCM Gen2 Tool Control Module TCMGen2 Device Control Module DCM Servo AmplifierCommunications Control Module CCM 39-30-41365 Communications Control Module CCM OptionalBackplane Fuses BackplanePower Supply Ground Fault Circuit Interrupter GfciDIP Switch Settings Circuit Breaker/Fuses Disconnect SwitchThis page is left blank intentionally Mounting the CS7000 Controller Installing the CS7000 ControllerEmissions and Susceptibility CS7000 Controller Dimensions of the Front and Bottom PanelInput Power Protection Meeting the AC Input Power RequirementsGrounding WiringWhite wire internal Active means an input is connected to +24VDC. Inactive Need to wire 24VDC to the output terminals for sourcing Tool Connector 26 pin Metal SMC Front View Connector Pinout DefinitionsConnector Front View TCM in and OUT Network Connectors Front ViewRS-232 Connector Front View Printer/Computer/Diagnostics RS-232 Connector Front View Programming the CS7000 Controller In GeneralProgramming the CS7000 with Ethernet CCM Cleaning the Enclosure Window Replacement PartsAssembly Drawings Technical InformationAnother country Contact InformationIndex Index-5-2 39-30-41365 This page left blank intentionally English