Trane BACnet Option Module How to Configure the System, Control Word Timeout Function, Bibbs

Page 23

How to Configure the System

Digital/Bus settings

 

Name

Par. Number

Default Value

Setting for BACnet

 

 

 

Coasting Select

8-50

Logic-or

Logic-or

 

 

 

Quick Stop Select

8-51

Logic-or

Logic-or

 

 

 

DC Brake Select

8-52

Logic-or

Logic-or

 

 

 

Start Select

8-53

Logic-or

Logic-or

 

 

 

Reversing Select

8-54

Logic-or

Logic-or

 

 

 

Set-up Select

8-55

Logic-or

Logic-or

 

 

 

Preset reference Select

8-56

Logic-or

Logic-or

 

 

 

 

 

 

 

 

 

BACnet settings

 

 

 

 

 

 

Name

Par. Number

Default Value

Setting for BACnet

 

 

 

BACnet device instance

8-71

1

1

 

 

 

MS/TP Max Masters

8-73

127

Depent on the Number of

 

 

 

Masters in the system

 

 

 

 

 

 

 

 

 

“I am” Service

8-74

At power-up

At power-up

 

 

 

Initialization Password

8-75

“admin”

“admin”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Word Timeout Function

par.8-03Control Timeout Time and par.8-04Control Timeout Function are not enabled in this version of the BACnet option.

BIBBs

Bibb's

ReadProperty Service

ReadPropertyMultiple Service

WriteProperty Service

WritePropertyMultiple Service

ConfirmedEventNotification Service

UnconfirmedEventNotification Service

GetEventInformation Service

AcknowledgeAlarm Service

ReinitializeDevice Service

DeviceCommunicationControl Service

I-Have Service

Who-Has Service

Who-Is Service

I-am Service

TimeSynchronization

4-2

TR200 BACnet

Image 23
Contents TR200 Introduction LED Status Copyright, limitation of liability and revision rights SafetySafety Safety Regulations Safety High Voltage WarningSafety Note Installation at high altitudes Min. Waiting Time Minutes VoltageSafety Safety Precautions Protection Mode Electrical ratings Safety Before Commencing Repair WorkInstallation requirements Technical Overview IntroductionAbout this Manual Transport mechanism Physical characteristicsIntroduction Background informationAvailable Literature for TR200 Introduction AssumptionsBackground Knowledge LED MAV MOC MRV Introduction AbbreviationsInstallation of the Option How to InstallCable lengths and number of nodes How to InstallCabling InstructionsHow to Install Maximum Cable Lengths How to Install Network TerminationConnecting the Bus Line Connection of the Cable Shield How to Install Cable RoutingEMC Precautions How to Install Ground Connection Initialization Parameter How to Configure the SystemInitialization Procedure Bibbs How to Configure the SystemControl Word Timeout Function Name Par. number Value How to Configure the System Closed-loop How to Control the Adjustable Frequency DriveReference Handling Open-loopAnalog Input and Output Objects How to Control the Adjustable Frequency DriveRameter Notifi Timeout Scription Rameter Bus Change- Non-vola Alarm Triggers Object Name Able DeCation Timeout ObjectNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Object Name Able De Change Non-vola AlarmWrite Timeout Scription Triggers Bus Timeout How to Control the Adjustable Frequency DriveChange Non-vola Alarm Object Name Able De BV80 Broken Belt BV121 10V low BV156 Reserved, P Drive Par Write Change- Non-vola Alarm Object Name Able DeMulti-state Input and Output Objects Write Scription Real Time Clock VariableObject Read Change- Non-vola Adjustable Frequency Drive Feedback to Network Value Class Output ValueOutput Value Stage Multi Stage File value Event notifi- cation class Object / Property Support Matrix Device BinaryHow to Control the Adjustable Frequency Drive Parameter List Title Default value Range Conver Data Sion index TypeParameters Control Site Control Timeout TimeParameters Comm. and OptionsEnd-of-Timeout Function Control Timeout FunctionProtocol Reset Control TimeoutDiagnosis Trigger Control ProfileParity / Stop Bits ParametersAddress Baud RateCoasting Select Minimum Response DelayMax Response Delay Max Inter-Char DelaySet-up Select Start SelectReverse Select 72 MS/TP Max Masters Preset Reference SelectInitialization Password BACnet Device InstanceGeneral TroubleshootingAlarm and Warning Messages AlarmsBit Alarm Word Hex Par.16-90 Alarm Word Troubleshooting Alarm WordsAlarm word, par.16-90 Alarm Word Alarm word 2, par.16-91 Alarm wordBit TroubleshootingBit Hex Par.16-92 Warning Word LED 2 Module Status Phases Status Bi-color LEDLED 1 Net Status MG12L122 *MG12L122