Trane TR200, BACnet Option Module instruction manual Name Par. number Value

Page 24

How to Configure the System

Example of a simple set-up of BACnet

This example shows the necessary steps to set up the TR200 BACnet interface with the following system re- quirements:

MS/TP running at 38,400 baud

MAC address 20 for the TR200

BACnet Device Instance 0 1025

Highest number of a master stack is 35

Start/stop of drive from BACnet only

Reference from BACnet

Read status of drive (actual speed)

Set the following parameters:

 

Name

Par. number

Value

 

 

Protocol

8-30

Drive option [9]

 

 

Address

8-31

20

 

 

Drive Port Baud Rate

8-32

38,400 Baud [4]

 

 

Coasting Select

8-50

Bus [1]

 

 

BACnet device instance

8-70

1025

 

 

MS/TP Max Masters

8-72

35

 

 

 

 

 

 

After the parameters have been set according to the table above, the drive has to be unpowered and repowered before the changes take effect. When the adjustable frequency drive is detected by the BMS, the drive can be

controlled by BV:1, which will start the motor if set to [1]. Setting AV:0 will set the speed reference of the drive. The actual speed can be monitored via AV:1. See also Analog Input and Output Objects section.

TR200 BACnet

4-3

Image 24
Contents TR200 Introduction LED Status Safety Copyright, limitation of liability and revision rightsSafety Safety High Voltage Warning Safety NoteSafety Regulations Installation at high altitudes Voltage Min. Waiting Time MinutesSafety Safety Precautions Protection Mode Safety Before Commencing Repair Work Installation requirementsElectrical ratings Introduction About this ManualTechnical Overview Physical characteristics IntroductionBackground information Transport mechanismIntroduction Assumptions Background KnowledgeAvailable Literature for TR200 Introduction Abbreviations LED MAV MOC MRVHow to Install Installation of the OptionHow to Install CablingInstructions Cable lengths and number of nodesHow to Install How to Install Network Termination Connecting the Bus LineMaximum Cable Lengths How to Install Cable Routing EMC PrecautionsConnection of the Cable Shield How to Install Ground Connection How to Configure the System Initialization ProcedureInitialization Parameter How to Configure the System Control Word Timeout FunctionBibbs Name Par. number Value How to Configure the System How to Control the Adjustable Frequency Drive Reference HandlingOpen-loop Closed-loopHow to Control the Adjustable Frequency Drive Analog Input and Output ObjectsRameter Notifi Timeout Scription Rameter Change- Non-vola Alarm Triggers Object Name Able De Cation TimeoutObject BusNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Change Non-vola Alarm Write Timeout ScriptionObject Name Able De How to Control the Adjustable Frequency Drive Change Non-vola Alarm Object Name Able DeTriggers Bus Timeout BV80 Broken Belt BV121 10V low BV156 Reserved, P Change- Non-vola Alarm Object Name Able De Multi-state Input and Output ObjectsDrive Par Write Real Time Clock Variable Object Read Change- Non-volaWrite Scription Adjustable Frequency Drive Feedback to Network Output Value Output Value StageValue Class Object / Property Support Matrix Device Binary Multi Stage File value Event notifi- cation classHow to Control the Adjustable Frequency Drive Title Default value Range Conver Data Sion index Type ParametersParameter List Control Timeout Time ParametersComm. and Options Control SiteControl Timeout Function End-of-Timeout FunctionReset Control Timeout Diagnosis TriggerControl Profile ProtocolParameters AddressBaud Rate Parity / Stop BitsMinimum Response Delay Max Response DelayMax Inter-Char Delay Coasting SelectStart Select Reverse SelectSet-up Select Preset Reference Select Initialization PasswordBACnet Device Instance 72 MS/TP Max MastersTroubleshooting Alarm and Warning MessagesAlarms GeneralTroubleshooting Alarm Words Alarm word, par.16-90 Alarm WordAlarm word 2, par.16-91 Alarm word Bit Alarm Word Hex Par.16-90 Alarm WordTroubleshooting Bit Hex Par.16-92 Warning WordBit Phases Status Bi-color LED LED 1 Net StatusLED 2 Module Status MG12L122 *MG12L122