Parameters
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option:Function:
Select the timeout function. The timeout function is activated when the control word fails to be updated within the time period specified in par.
[0] * | Off |
[1]Freeze output
[2]Stop
[3]Jogging
[4]Max. speed
[5]Stop and trip
[7]Select setup 1
[8]Select setup 2
[9]Select setup 3
[10]Select setup 4
[20]N2 Override Release
In LonWorks, the timeout function is also activated when the following SNVTs fail to be updated within the time period specified in
nviStartStop | nviDrvSpeedStpt |
nviReset Fault | nviRefPcnt |
nviControlWord | nviRefHz |
8-05 End-of-Timeout Function
Option: |
| Function: | ||||||
|
| Select the action after receiving a valid control word following a timeout. | ||||||
|
| This parameter is active only when | ||||||
|
| set to |
|
| ||||
|
|
|
|
|
|
|
|
|
[0] | Hold | Retains the | ||||||
|
|
|
|
|
|
| ||
|
| displays a warning, until | ||||||
|
|
|
|
| ||||
|
| the adjustable frequency drive resumes its original | ||||||
|
|
|
|
|
|
|
|
|
[1] * | Resume | Resumes the | ||||||
|
|
|
|
|
|
|
|
|