Trane TR200, BACnet Option Module Control Timeout Function, End-of-Timeout Function

Page 46

Parameters

nviControlWord

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

8-04 Control Timeout Function

Option:Function:

Select the timeout function. The timeout function is activated when the control word fails to be updated within the time period specified in par. 8-03Control Timeout Time. Choice [20] only appears after setting the Metasys N2 protocol.

[0] *

Off

[1]Freeze output

[2]Stop

[3]Jogging

[4]Max. speed

[5]Stop and trip

[7]Select setup 1

[8]Select setup 2

[9]Select setup 3

[10]Select setup 4

[20]N2 Override Release

In LonWorks, the timeout function is also activated when the following SNVTs fail to be updated within the time period specified in par.8-03Control Timeout Time:

nviStartStop

nviDrvSpeedStpt

nviReset Fault

nviRefPcnt

nviControlWord

nviRefHz

8-05 End-of-Timeout Function

Option:

 

Function:

 

 

Select the action after receiving a valid control word following a timeout.

 

 

This parameter is active only when par.8-04Control Timeout Function is

 

 

set to [Set-up 1-4].

 

 

 

 

 

 

 

 

 

 

 

[0]

Hold set-up

Retains the set-up selected in par.8-04Control Timeout Function and

 

 

 

 

 

 

 

 

 

displays a warning, until par.8-06Reset Control Timeout toggles. Then

 

 

 

 

 

 

 

the adjustable frequency drive resumes its original set-up.

 

 

 

 

 

 

 

 

 

[1] *

Resume set-up

Resumes the set-up active prior to the timeout.

 

 

 

 

 

 

 

 

 

TR200 BACnet

6-3

Image 46
Contents TR200 Introduction LED Status Safety Copyright, limitation of liability and revision rightsSafety Safety Note Safety High Voltage WarningSafety Regulations Installation at high altitudes Voltage Min. Waiting Time MinutesSafety Safety Precautions Protection Mode Installation requirements Safety Before Commencing Repair WorkElectrical ratings About this Manual IntroductionTechnical Overview Background information Physical characteristicsIntroduction Transport mechanismBackground Knowledge Introduction AssumptionsAvailable Literature for TR200 Introduction Abbreviations LED MAV MOC MRVHow to Install Installation of the OptionInstructions How to InstallCabling Cable lengths and number of nodesHow to Install Connecting the Bus Line How to Install Network TerminationMaximum Cable Lengths EMC Precautions How to Install Cable RoutingConnection of the Cable Shield How to Install Ground Connection Initialization Procedure How to Configure the SystemInitialization Parameter Control Word Timeout Function How to Configure the SystemBibbs Name Par. number Value How to Configure the System Open-loop How to Control the Adjustable Frequency DriveReference Handling Closed-loopHow to Control the Adjustable Frequency Drive Analog Input and Output ObjectsRameter Notifi Timeout Scription Rameter Object Change- Non-vola Alarm Triggers Object Name Able DeCation Timeout BusNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Write Timeout Scription Change Non-vola AlarmObject Name Able De Change Non-vola Alarm Object Name Able De How to Control the Adjustable Frequency DriveTriggers Bus Timeout BV80 Broken Belt BV121 10V low BV156 Reserved, P Multi-state Input and Output Objects Change- Non-vola Alarm Object Name Able DeDrive Par Write Object Read Change- Non-vola Real Time Clock VariableWrite Scription Adjustable Frequency Drive Feedback to Network Output Value Stage Output ValueValue Class Object / Property Support Matrix Device Binary Multi Stage File value Event notifi- cation classHow to Control the Adjustable Frequency Drive Parameters Title Default value Range Conver Data Sion index TypeParameter List Comm. and Options Control Timeout TimeParameters Control SiteControl Timeout Function End-of-Timeout FunctionControl Profile Reset Control TimeoutDiagnosis Trigger ProtocolBaud Rate ParametersAddress Parity / Stop BitsMax Inter-Char Delay Minimum Response DelayMax Response Delay Coasting SelectReverse Select Start SelectSet-up Select BACnet Device Instance Preset Reference SelectInitialization Password 72 MS/TP Max MastersAlarms TroubleshootingAlarm and Warning Messages GeneralAlarm word 2, par.16-91 Alarm word Troubleshooting Alarm WordsAlarm word, par.16-90 Alarm Word Bit Alarm Word Hex Par.16-90 Alarm WordBit Hex Par.16-92 Warning Word TroubleshootingBit LED 1 Net Status Phases Status Bi-color LEDLED 2 Module Status MG12L122 *MG12L122