Trane BACnet Option Module Minimum Response Delay, Max Response Delay, Max Inter-Char Delay

Page 49

Parameters

8-35 Minimum Response Delay

Range:

Function:

10. ms* [5. - 10000. ms]

Specify the minimum delay time between receiving a request and trans-

 

mitting a response. This is used for overcoming modem turnaround

 

delays.

 

 

8-36 Max Response Delay

Range:

Function:

10001. [11. - 10001. ms]

Specify the maximum permissible delay time between transmitting a re-

ms*

quest and receiving a response. Exceeding this delay time will cause

 

control word timeout.

 

 

8-37 Max Inter-Char Delay

Range:

Function:

25.00 [0.00 - 35.00 ms]

Specify the maximum permissible time interval between receiving two

ms*

bytes. This parameter activates timeout if transmission is interrupted.

 

 

8-50

Coasting Select

 

Option:

 

Function:

 

 

 

 

 

Select control of the coasting function via the terminals (digital input)

 

 

and/or via the bus.

 

 

 

[0]

Digital input

Activates Start command via a digital input.

 

 

 

[1]

Bus

Activates Start command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Start command via the serial communication bus/serial com-

 

 

munication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates Start command via the serial communication bus/serial com-

 

 

munication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

8-52 DC Brake Select

Option:

 

Function:

 

 

Select control of the DC brake via the terminals (digital input) and/or via

 

 

the serial communication bus.

 

 

 

[0]

Digital input

Activates Start command via a digital input.

 

 

 

[1]

Bus

Activates Start command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Start command via the serial communication bus/serial com-

 

 

munication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates Start command via the serial communication bus/serial com-

 

 

munication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

6-6

TR200 BACnet

Image 49
Contents TR200 Introduction LED Status Copyright, limitation of liability and revision rights SafetySafety Safety Note Safety High Voltage WarningSafety Regulations Installation at high altitudes Min. Waiting Time Minutes VoltageSafety Safety Precautions Protection Mode Installation requirements Safety Before Commencing Repair WorkElectrical ratings About this Manual IntroductionTechnical Overview Introduction Physical characteristicsBackground information Transport mechanismBackground Knowledge Introduction AssumptionsAvailable Literature for TR200 LED MAV MOC MRV Introduction AbbreviationsInstallation of the Option How to InstallCabling How to InstallInstructions Cable lengths and number of nodesHow to Install Connecting the Bus Line How to Install Network TerminationMaximum Cable Lengths EMC Precautions How to Install Cable RoutingConnection of the Cable Shield How to Install Ground Connection Initialization Procedure How to Configure the SystemInitialization Parameter Control Word Timeout Function How to Configure the SystemBibbs Name Par. number Value How to Configure the System Reference Handling How to Control the Adjustable Frequency DriveOpen-loop Closed-loopAnalog Input and Output Objects How to Control the Adjustable Frequency DriveRameter Notifi Timeout Scription Rameter Cation Timeout Change- Non-vola Alarm Triggers Object Name Able DeObject BusNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Write Timeout Scription Change Non-vola AlarmObject Name Able De Change Non-vola Alarm Object Name Able De How to Control the Adjustable Frequency DriveTriggers Bus Timeout BV80 Broken Belt BV121 10V low BV156 Reserved, P Multi-state Input and Output Objects Change- Non-vola Alarm Object Name Able DeDrive Par Write Object Read Change- Non-vola Real Time Clock VariableWrite Scription Adjustable Frequency Drive Feedback to Network Output Value Stage Output ValueValue Class Multi Stage File value Event notifi- cation class Object / Property Support Matrix Device BinaryHow to Control the Adjustable Frequency Drive Parameters Title Default value Range Conver Data Sion index TypeParameter List Parameters Control Timeout TimeComm. and Options Control SiteEnd-of-Timeout Function Control Timeout FunctionDiagnosis Trigger Reset Control TimeoutControl Profile ProtocolAddress ParametersBaud Rate Parity / Stop BitsMax Response Delay Minimum Response DelayMax Inter-Char Delay Coasting SelectReverse Select Start SelectSet-up Select Initialization Password Preset Reference SelectBACnet Device Instance 72 MS/TP Max MastersAlarm and Warning Messages TroubleshootingAlarms GeneralAlarm word, par.16-90 Alarm Word Troubleshooting Alarm WordsAlarm word 2, par.16-91 Alarm word Bit Alarm Word Hex Par.16-90 Alarm WordBit Hex Par.16-92 Warning Word TroubleshootingBit LED 1 Net Status Phases Status Bi-color LEDLED 2 Module Status MG12L122 *MG12L122