Trane BACnet Option Module, TR200 Parameters, Comm. and Options, Control Site, Control Source

Page 45

Parameters

Parameter Description

8-** Comm. and Options

Parameter group for configuring communications and options.

8-01

Control Site

 

 

 

 

 

Option:

 

Function:

 

 

 

 

 

 

 

 

 

The setting in this parameter overrides the settings in par.8-50Coasting

 

 

Select to par.8-56Preset Reference Select.

 

 

 

 

 

 

 

 

 

[0] *

Digital and ctrl. word

Control by using both digital input and control word.

 

 

 

 

 

 

 

[1]

Digital only

Control by using digital inputs only.

 

 

 

 

 

 

 

[2]

Control word only

Control by using control word only.

8-02 Control Source

Option:Function:

Select the source of the control word: one of two serial interfaces or four

installed options. During initial power-up, the adjustable frequency drive automatically sets this parameter to Option A [3] if it detects a valid serial

communication bus option installed in slot A. If the option is removed,

the adjustable frequency drive detects a change in the configuration, sets par.8-02Control Source back to default setting Adjustable Frequency Drive Port, and the adjustable frequency drive then trips. If an option is

installed after initial power-up, the setting of par.8-02Control Source will not change but the adjustable frequency drive will trip and display: Alarm

67Option Changed.

[0]None

[1]FC RS-485

[2]FC USB

[3]* Option A

[4]Option B

[5]Option C0

[6]Option C1

[30]External Can

NOTE: This parameter cannot be adjusted while the motor is running.

8-03 Control Timeout Time

Range:

Function:

60.0 s* [1.0 - 18000.0 s]

Enter the maximum time expected to pass between the reception of two

 

consecutive messages. If this time is exceeded, it indicates that the serial

 

communication has stopped. The function selected in par.8-04Control

 

 

 

 

 

 

Timeout Function Control Timeout Function will then be carried out.

 

 

 

 

In LonWorks, the following variables will trigger the Control Word Time

 

parameter:

 

nviStartStop

 

nviReset Fault

 

 

 

 

 

6-2

TR200 BACnet

Image 45
Contents TR200 Introduction LED Status Copyright, limitation of liability and revision rights SafetySafety Safety High Voltage Warning Safety NoteSafety Regulations Installation at high altitudes Min. Waiting Time Minutes VoltageSafety Safety Precautions Protection Mode Safety Before Commencing Repair Work Installation requirementsElectrical ratings Introduction About this ManualTechnical Overview Introduction Physical characteristicsBackground information Transport mechanismIntroduction Assumptions Background KnowledgeAvailable Literature for TR200 LED MAV MOC MRV Introduction AbbreviationsInstallation of the Option How to InstallCabling How to InstallInstructions Cable lengths and number of nodesHow to Install How to Install Network Termination Connecting the Bus LineMaximum Cable Lengths How to Install Cable Routing EMC PrecautionsConnection of the Cable Shield How to Install Ground Connection How to Configure the System Initialization ProcedureInitialization Parameter How to Configure the System Control Word Timeout FunctionBibbs Name Par. number Value How to Configure the System Reference Handling How to Control the Adjustable Frequency DriveOpen-loop Closed-loopAnalog Input and Output Objects How to Control the Adjustable Frequency DriveRameter Notifi Timeout Scription Rameter Cation Timeout Change- Non-vola Alarm Triggers Object Name Able DeObject BusNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Change Non-vola Alarm Write Timeout ScriptionObject Name Able De How to Control the Adjustable Frequency Drive Change Non-vola Alarm Object Name Able DeTriggers Bus Timeout BV80 Broken Belt BV121 10V low BV156 Reserved, P Change- Non-vola Alarm Object Name Able De Multi-state Input and Output ObjectsDrive Par Write Real Time Clock Variable Object Read Change- Non-volaWrite Scription Adjustable Frequency Drive Feedback to Network Output Value Output Value StageValue Class Multi Stage File value Event notifi- cation class Object / Property Support Matrix Device BinaryHow to Control the Adjustable Frequency Drive Title Default value Range Conver Data Sion index Type ParametersParameter List Parameters Control Timeout TimeComm. and Options Control SiteEnd-of-Timeout Function Control Timeout FunctionDiagnosis Trigger Reset Control TimeoutControl Profile ProtocolAddress ParametersBaud Rate Parity / Stop BitsMax Response Delay Minimum Response DelayMax Inter-Char Delay Coasting SelectStart Select Reverse SelectSet-up Select Initialization Password Preset Reference SelectBACnet Device Instance 72 MS/TP Max MastersAlarm and Warning Messages TroubleshootingAlarms GeneralAlarm word, par.16-90 Alarm Word Troubleshooting Alarm WordsAlarm word 2, par.16-91 Alarm word Bit Alarm Word Hex Par.16-90 Alarm WordTroubleshooting Bit Hex Par.16-92 Warning WordBit Phases Status Bi-color LED LED 1 Net StatusLED 2 Module Status MG12L122 *MG12L122