How to Control the Adjustable Frequency

Drive

 

 

Object

Object Name

Read/

Change-

Non-vola-

TR200Pa-

Alarm

Triggers Bus

 

 

 

 

ID

Write

able De-

tile RAM

rameter

notifi-

Timeout

 

 

 

 

 

scription

Store

cation

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:0

Reference

W/R

Yes

No

MRV

No

Yes

 

 

 

 

AV:1

Speed Act. Value

W/R

Yes

No

MAV

Yes

Yes

 

 

 

 

AV:2

Bus Feedback1

W/R

Yes

No

8-94

No

Yes

 

 

 

 

AV:3

Bus Feedback2

W/R

Yes

No

8-95

No

Yes

 

 

 

 

AV:4

Bus Feedback3

W/R

Yes

No

8-96

No

Yes

 

 

 

 

AV:5

Motor Voltage

Read

Yes

No

16-12

Yes

No

 

 

 

 

AV:6

Motor Current

Read

Yes

No

16-14

Yes

No

 

 

 

 

AV:7

Motor Torque %

Read

Yes

No

16-22

Yes

No

 

 

 

 

AV:8

DC Link Voltage

Read

Yes

No

16-30

Yes

No

 

 

 

 

AV:9

Motor Thermal

Read

Yes

No

16-18

Yes

No

 

 

 

 

AV:10

Heatsink Temper-

Read

Yes

No

16-34

Yes

No

 

 

 

 

ature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:11

Inverter Thermal

Read

Yes

No

16-35

Yes

No

 

 

 

 

AV:12

Operating Hours

Read

No

No

15-00

No

No

 

 

 

 

AV:13

Running Hours

Read

No

No

15-01

No

No

 

 

 

 

AV:14

KWh Counter

Read

No

No

15-02

No

No

 

 

 

 

AV:15

Power [KW]

Read

No

No

16-10

No

No

 

 

 

 

AV:16

PID Start Speed

W/R

No

TR200

20-83

No

No

 

 

 

 

[Hz]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:17

PID Proportional

W/R

No

TR200

20-93

No

No

 

 

 

 

Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:18

PID Integral Time

W/R

No

TR200

20-94

No

No

 

 

 

 

(Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:19

PID Differential

W/R

No

TR200

20-95

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:20

PID Dif. Gain Limit

W/R

No

TR200

20-96

No

No

 

 

 

 

AV:21

On Reference

W/R

No

TR200

20-84

No

No

 

 

 

 

Bandwith

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:22

Ext. 1 Setpoint

W/R

No

TR200

21-15

No

No

 

 

 

 

AV:23

Ext. 1 Reference

W/R

No

TR200

21-17

No

No

 

 

 

 

[Unit]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:24

Ext. 1 Feedback

W/R

No

TR200

21-18

No

No

 

 

 

 

[Unit]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:25

Ext. 1 Proportion-

W/R

No

TR200

21-21

No

No

 

 

 

 

al Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:26

Reserved

W/R

No

Na

 

 

 

 

 

 

 

AV:27

Ext. 1 Integral

W/R

No

TR200

21-22

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:28

Ext. 1 Differential

W/R

No

TR200

21-23

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:29

Ext. 1 Dif. Gain

W/R

No

TR200

21-24

No

No

 

 

 

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:30

Reserved

W/R

No

Na

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5. 3: Analog values

TR200 BACnet

5-3

Image 28
Contents TR200 Introduction LED Status Safety Copyright, limitation of liability and revision rightsSafety Safety Note Safety High Voltage WarningSafety Regulations Installation at high altitudes Voltage Min. Waiting Time MinutesSafety Safety Precautions Protection Mode Installation requirements Safety Before Commencing Repair WorkElectrical ratings About this Manual IntroductionTechnical Overview Physical characteristics IntroductionBackground information Transport mechanismBackground Knowledge Introduction AssumptionsAvailable Literature for TR200 Introduction Abbreviations LED MAV MOC MRVHow to Install Installation of the OptionHow to Install CablingInstructions Cable lengths and number of nodesHow to Install Connecting the Bus Line How to Install Network TerminationMaximum Cable Lengths EMC Precautions How to Install Cable RoutingConnection of the Cable Shield How to Install Ground Connection Initialization Procedure How to Configure the SystemInitialization Parameter Control Word Timeout Function How to Configure the SystemBibbs Name Par. number Value How to Configure the System How to Control the Adjustable Frequency Drive Reference HandlingOpen-loop Closed-loopHow to Control the Adjustable Frequency Drive Analog Input and Output ObjectsRameter Notifi Timeout Scription Rameter Change- Non-vola Alarm Triggers Object Name Able De Cation TimeoutObject BusNon-vola Alarm Triggers Bus Able De BO30 Reserved Output Write Timeout Scription Change Non-vola AlarmObject Name Able De Change Non-vola Alarm Object Name Able De How to Control the Adjustable Frequency DriveTriggers Bus Timeout BV80 Broken Belt BV121 10V low BV156 Reserved, P Multi-state Input and Output Objects Change- Non-vola Alarm Object Name Able DeDrive Par Write Object Read Change- Non-vola Real Time Clock VariableWrite Scription Adjustable Frequency Drive Feedback to Network Output Value Stage Output ValueValue Class Object / Property Support Matrix Device Binary Multi Stage File value Event notifi- cation classHow to Control the Adjustable Frequency Drive Parameters Title Default value Range Conver Data Sion index TypeParameter List Control Timeout Time ParametersComm. and Options Control SiteControl Timeout Function End-of-Timeout FunctionReset Control Timeout Diagnosis TriggerControl Profile ProtocolParameters AddressBaud Rate Parity / Stop BitsMinimum Response Delay Max Response DelayMax Inter-Char Delay Coasting SelectReverse Select Start SelectSet-up Select Preset Reference Select Initialization PasswordBACnet Device Instance 72 MS/TP Max MastersTroubleshooting Alarm and Warning MessagesAlarms GeneralTroubleshooting Alarm Words Alarm word, par.16-90 Alarm WordAlarm word 2, par.16-91 Alarm word Bit Alarm Word Hex Par.16-90 Alarm WordBit Hex Par.16-92 Warning Word TroubleshootingBit LED 1 Net Status Phases Status Bi-color LEDLED 2 Module Status MG12L122 *MG12L122