Dell DL4000 owner manual Environmental, Operating Altitude De-rating, Particulate Contamination

Page 86

Environmental

Operating

3048 m (10,000 ft).

Storage

12,000 m (39,370 ft).

Operating Altitude De-rating

Up to 35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft).

35 °C to 40

°C (95 °F to 104 °F)

Maximum temperature is reduced by 1 °C/175 m (1 °F/319

 

 

ft) above 950 m (3,117 ft).

40 °C to 45

°C (104 °F to 113 °F)

Maximum temperature is reduced by 1 °C/125 m (1 °F/228

 

 

ft) above 950 m (3,117 ft).

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.

Air Filtration

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Conductive Dust

NOTE: Applies to data center and non-data center environments.

Corrosive Dust

NOTE: Applies to data center and non-data center environments.

Gaseous Contamination

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less than 60% relative humidity.

NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.

Copper Coupon Corrosion Rate

<300 Å/month per Class G1 as defined by ANSI/

 

ISA71.04-1985.

Silver Coupon Corrosion Rate

<200 Å/month as defined by AHSRAE TC9.9.

86

Image 86
Contents Regulatory Model E16S Series Regulatory Type E16S001 Dell Inc Contents Installing The Cooling Shroud Troubleshooting Your System Using System DiagnosticsGetting Help Jumpers And ConnectorsTechnical Specifications System Messages Front-Panel Features And Indicators Indicator, Button, or Icon Description ConnectorCorrective Action Diagnostic IndicatorsElectrical indicator Condition Drive-Status Condition Indicator Pattern RAID Only Hard-Drive Indicator PatternsError occurs Amber if a memoryBack-Panel Features And Indicators SecondsGreen Link indicator is NIC Indicator CodesPower Indicator Codes Other Information You May Need Guide Release Notes Getting StartedGuide Manuals Users Guide Page Entering System Setup Using The System Setup Navigation Keys System Setup OptionsResponding To Error Messages System Setup Main ScreenMemory Settings Screen System Information ScreenProcessor Settings Screen Sata Settings Screen Boot Settings ScreenIntegrated Devices Screen System Profile Settings Screen Serial Communications ScreenSystem Security Screen Miscellaneous Settings Set to Enabled System And Setup Password FeaturesAssigning a System And/Or Setup Password Using Your System Password To Secure Your System Entering The iDRAC Settings Utility IDRAC Settings UtilityOperating With a Setup Password Enabled Embedded System ManagementRemoving The Front Bezel Recommended ToolsFront Bezel Optional Opening The System Installing The Front BezelOpening And Closing The System Inside The System Closing The SystemCooling Shroud Removing The Cooling ShroudInstalling The Cooling Shroud System MemoryProcessor Channel 0 slots A1, A5, and A9Removing Memory Modules Memory ConfigurationMode-Specific Guidelines Number Dimm Rank Dimm Slot PopulationMemory module/memory-module blank Installing Memory Modules TimeInstalling The Memory Module Hard DrivesInstalling a Hot-Swap Hard Drive Removing a Hot-Swap Hard DriveRemoving a Hard Drive From a Hard-Drive Carrier Removing a Cooling Fan Installing a Hard Drive Into a Hard-Drive CarrierCooling Fans Expansion Cards And Expansion-Card Risers Installing a Cooling FanExpansion Card Installation Guidelines Height Length Link Width Slot Width Removing An Expansion CardRiser PCIe Slot Card Priority Card Type Slot Priority Max AllowedInstalling An Expansion Card Removing and Installing the Expansion CardRemoving and Installing the Expansion Card Riser Removing Expansion-Card RisersInstalling Expansion-Card Risers SD vFlash CardRemoving The Internal Dual SD Module Internal Dual SD ModuleReplacing An SD vFlash Card Installing The Internal Dual SD Module Removing and Installing the Internal Dual SD ModuleIntegrated Storage Controller Card Installing An Internal SD CardInternal SD Card Removing An Internal SD CardRemoving The Integrated Storage Controller Removing The Network Daughter Card Installing The Integrated Storage ControllerNetwork Daughter Card Installing The Network Daughter Card ProcessorsRemoving a Processor Removing and Installing the Heat Sink Close-lock symbol Installing a Processor Removing and Installing a ProcessorPower Supplies Your system supports two 750 W power suppliesHot Spare Feature Removing An AC Power SupplyReplacing The System Battery System BatteryInstalling An AC Power Supply Removing the System Battery Cover Hard-Drive Backplane Removing The Hard-Drive BackplaneBackplane signal cable SD card socket Installing The Hard-Drive Backplane Cabling Diagram-2.5 Inch SystemsControl Panel Assembly Removing The Control PanelInstalling The Control Panel Removing and Installing the Control PanelSystem Board Removing The System BoardSystem board System-board holder Release pin Installing The System Board Troubleshooting a USB Device Troubleshooting External ConnectionsTroubleshooting The Video Subsystem Troubleshooting a Serial I/O Device Troubleshooting a NICTroubleshooting a Wet System Troubleshooting a Damaged SystemTroubleshooting The System Battery Troubleshooting Power SuppliesTroubleshooting System Memory Troubleshooting Cooling ProblemsTroubleshooting Cooling Fans Troubleshooting An SD Card Reseat the memory modules in their sockets Close the systemTroubleshooting a Hard Drive Troubleshooting a Storage ControllerTroubleshooting Expansion Cards Troubleshooting Processors Page Running The Embedded System Diagnostics Dell Online Diagnostics Dell Embedded System DiagnosticsWhen To Use The Embedded System Diagnostics System Diagnostic Controls Least one event description is recordedSystem Board Jumper Settings Jumper Setting DescriptionSystem Board Connectors Connector DescriptionJCOM1 Disabling a Forgotten Password Configuration Drives Expansion slots using riser cardConfiguration High Capacity Connectors BackFront Connectors High CapacityExpanded Operating Temperature InternalRelative Humidity Environmental TemperatureTemperature Continuous Operation Maximum VibrationParticulate Contamination EnvironmentalOperating Altitude De-rating Gaseous ContaminationSystem Error Messages ASR0003 Message ASR0001 MessageASR0002 Message BAT0002 MessageCPU0010 Message CPU0001 MessageCPU0005 Message CPU0023 MessageCPU0702 Message CPU0701 Message CPU number protocol error detected DetailsException is external to the processor CPU0703 MessageDetails Fan operating speed is out of range Action Action Reinstall or reconnect the hardware HWC2003 MessageFAN0000 Message FAN0001 MessageMEM0701 Message MEM0001 MessageMEM0007 Message MEM0702 MessagePCI1304 Message MEM8000 MessagePCI1302 Message PCI1308 MessageConfigurations Reinstall the devicePDR0001 Message Fault detected on drive number Details PSU0001 Message Power supply number failed ActionPSU0006 Message PSU0002 MessagePSU0003 Message PSU0016 MessagePSU0035 Message PSU0033 MessagePSU0034 Message PSU0036 MessageConfiguration and power consumption PSU1201 Message Power supply redundancy is lost DetailsSystem power inventory change System power consumptionRFM2001 Message RFM1014 MessageRFM1201 Message RFM2002 MessagePower. If problem persists call support SEL0006 Message All event logging is disabled DetailsAppear if the user disabled event logging Issues persists, contact supportFailures TMP0119 MessageFailed TMP0121 MessageDiagnostic Messages Alert Messages102 Documentation Feedback Locating Your System Service TagContacting Dell
Related manuals
Manual 11 pages 38.93 Kb Manual 4 pages 41.95 Kb

DL4000 specifications

The Dell DL4000 is an innovative and robust data protection solution designed to meet the storage and backup needs of modern businesses. This appliance, part of Dell's Data Domain family, provides reliable data backup, recovery, and archiving, enhancing efficiency in managing critical business data.

One of the standout features of the DL4000 is its integration of advanced deduplication technology. This allows businesses to significantly reduce the amount of storage required for backup data by eliminating duplicate copies of files. The result is reduced storage costs and improved backup speeds, enabling organizations to save both time and resources.

The DL4000 also boasts scalable capacity, which is essential for growing businesses. With the ability to increase storage volume without significant infrastructure changes, organizations can easily adapt the appliance to changing data requirements. The product is available in various configurations, offering flexible options to meet diverse business needs.

Another key characteristic is its high performance in data protection tasks. The DL4000 provides quick backup and recovery capabilities, thanks to its efficient data processing algorithms. Organizations can restore critical data swiftly, minimizing downtime and ensuring business continuity in the event of data loss. The appliance supports multiple backup sources, including virtual machines, physical servers, and cloud environments, providing flexibility in data management.

Additionally, the DL4000 is equipped with robust security features. It supports encryption both at rest and in transit, ensuring that sensitive data is protected from unauthorized access. Compliance with industry regulations is simplified, aiding organizations in maintaining data integrity and confidentiality.

User-friendliness is another highlight of the Dell DL4000. The intuitive management interface allows IT administrators to monitor and manage backups with ease. Automation features help streamline backup processes, reducing the likelihood of human error and ensuring consistent data protection.

In conclusion, the Dell DL4000 offers a comprehensive data protection solution that combines advanced technologies with user-centric design. Its deduplication capabilities, scalability, high performance, security features, and ease of use make it an ideal choice for businesses looking to enhance their data backup and recovery strategies. Organizations investing in the DL4000 can be confident that they are adopting a powerful tool to safeguard their valuable data assets.