4. Advanced Operations
Enabling or Disabling a Load trap
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Switched PDU: prompt, type set trap infeed load, followed by the infeed name, and on or off. Press Enter, or
Type set trap infeed load all, followed by on or off and press Enter.
Examples
The following command enables the Load trap for second infeed on the first tower, using the infeed’s absolute name:
Switched PDU: set trap infeed load .AB on<Enter>
The following command disables the Load trap for all infeeds:
Switched PDU: set trap infeed load all off<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed Load trap automatically enables the Infeed and Tower Status traps for that infeed.
Setting the Infeed Load limit
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Switched PDU: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value from 0 to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using the infeed’s absolute name:
Switched PDU: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling a Change trap
The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the Switched PDU: prompt, type set trap outlet change, followed by the outlet name and on or off. Press Enter, or
Type set trap outlet change all, followed by on or off and press Enter.
Example
The following command enables the Change trap for the third outlet on the first infeed of the second tower, using the outlet’s absolute name:
Switched PDU: set trap outlet change .ba3 on<Enter>
Enabling or Disabling the Temp trap
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the Switched PDU: prompt, type set trap ths temp, followed by the sensor name and on or off. Press
Enter.
Example
The following command enables the Temp trap for the first
Switched PDU: set trap ths temp .a1 on<Enter>