MGE UPS Systems Switched PDU Outlet Control, Individual, Group, Operations, To select a group

Page 14
Outlet Control

3. Operations

Outlet Control

The Outlet Control section offers access to the Individual and Group outlet control pages. From the Individual and Group pages, the user can review and manipulate power control functions for all outlets and groups assigned to the current user. Both pages include the outlets absolute and descriptive names, the Outlet Status reported to the Switched PDU by the outlet, the current Control State being applied by the Switched PDU and the outlet load in amperes.

Available outlet and group power states may be set to on, off or reboot; the reboot operation turns the outlet(s) off, delays for a period of 15 seconds and then turns the outlet(s) on.

Individual

The Individual outlet control page displays all outlets assigned to the current user. The user may apply on, off or reboot actions to individual, multiple or all accessible outlets.

To apply actions to individual or multiple outlets:

In the Individual Outlet Control section, select the desired action from the Control Action drop-down menu for each individual outlet to be changed and press Apply.

To apply an action to all outlets:

In the Global Control section, select the desired action from the Control Action drop-down menu and press Apply.

Group

The Group outlet control page displays all groups assigned to the current user as well as the outlets for each group.

To select a group:

Select the group name from the drop-down menu and press Select. The page will refresh to display all outlets associated to the selected group name.

To apply an action to a group:

Select the desired action from the drop-down menu and press Apply.

Outlet State/Control State Field Values

Outlet State

Control State

Description

 

 

 

On

On

Outlet is on

 

 

 

Off

Off

Outlet is off

 

 

 

Off

Pend On

Outlet is off and about to turn on in response to a sequence timer

 

 

 

Off

Reboot

Outlet is off and a Reboot action has been initiated

 

 

 

On

Idle On

A restart has occurred – Last Control State has been maintained

 

 

 

Off

Idle Off

A restart has occurred – Last Control State has been maintained

 

 

 

On

Wake On

A power-loss has occurred – Wakeup State has been applied

 

 

 

Off

Wake Off

A power-loss has occurred – Wakeup State has been applied

 

 

 

On/Wait

Off

Outlet state in transition – Requery of outlet status required

 

 

 

Off/Wait

On

Outlet state in transition – Requery of outlet status required

 

 

 

On/Error

varies

Error State – Outlet should be off but current is sensed at the outlet

 

 

 

Off/Error

varies

Error State – Outlet should be on but no current is sensed at the outlet

 

 

 

No Comm

varies

Communication to the outlet has been lost*

 

 

 

 

 

* Control State will be applied when communication is re-established

Page 14 - 301-0399-4 Rev A.

Image 14
Contents Switched PDU Installation and user manual E T N I N U E H TProtective Grounding Terminal InstructionsDangerous Voltage Life-Support PolicyGETTING STARTED ContentsINSTALLATION OPERATIONSuser account prior to attachment to your network 1. Getting StartedQuick Start Guide Additional Required Items 2. InstallationStandard Accessories 1 Power Input 2 Input Current LED 3 Ethernet / RS232 Ports Equipment OverviewFigure 1. Unit Views 4 Temperature / Humidity PortsFigure 2. Retention Bracket assembly Safety PrecautionsInstalling the Power Input Retention Bracket To install the power input retention bracketTo connect to the power source Connecting to the Power SourceTo attach a power cord to the unit MountingConnecting to the Unit Connecting DevicesConnecting the Sensors Serial RS232 portPage HTML I NTERFACE 3. OperationsI NTERFACES C OMMAND L INE I NTERFACEInterfaces Usernames and Passwords3. Operations Outlet Naming and GroupingTo log in by HTML HTML InterfaceFigure 4. Example HTML page Logging In Group Outlet ControlIndividual Outlet State/Control State Field ValuesInput Load ConfigurationEnvironmental Monitoring SensorsHTTP/SSL NetworkTelnet/SSH Setting the IP address, subnet mask or gatewaySetting SSL access level Serial PortsSetting the HTTP authentication method Setting the data-rate for the serial portsUsers OutletsGroups Changing a user passwordAdding and Deleting group access Changing a user’s access privilege levelAdding and Deleting outlet access Adding and Deleting serial port accessSetting the filename for upload SNTPSNMP Testing the FTP upload configurationRestart Command Line InterfaceTools Logging InOperations Command Summary Administrative Command SummaryTo display the names of commands that you may execute Administrative Command Summary continuedTo reboot one or more outlets Operations CommandsRebooting outlets Turning outlets onDisplaying outlet status To display on/off status of one or more outletsDisplaying accessible groups Displaying accessible outletsTo display accessible outlets To display accessible groupsConnecting to a serial device Displaying accessible serial portsTo display accessible serial ports Displaying infeed statusStarting a new session Displaying the status of the Environmental MonitorTo display the status of the Environmental Monitor To start a new sessionCreating a user account Administration CommandsUser Administration To create a user accountSetting user access level privileges Changing a passwordTo change a password To set the access level privilege for a userAdding outlet access to a user Displaying the access privilege levelsTo display user access privilege levels To grant outlet access to a userAdding group access to a user Deleting outlet access for a userTo delete outlet access for a user To grant group access to a userTo display user outlet, group and serial port access Group AdministrationDisplaying user outlet, group and serial port access Creating a group nameTo add an outlet to a group Outlet AdministrationAdding an outlet to a group Deleting an outlet from a groupDisplaying outlet information Setting the outlet wakeup stateTo set the wakeup state To display outlet informationEnabling or disabling active signal checking for serial connections Serial Port AdministrationSetting the serial ports data-rate To enable or disable active signal checking for serial connectionsTo display system configuration information System AdministrationDisplaying system configuration information Creating a location descriptionDisplaying tower information Creating a descriptive tower nameTo create a tower name To display tower informationSetting the IP address TCP/IP AdministrationTo perform a warm boot Setting the subnet maskTo display network configuration information HTTP AdministrationDisplaying network configuration information To enable or disable HTTP supportTo set the HTTP authentication method Telnet AdministrationFTP Administration To enable or disable Telnet supportSetting the filename to be uploaded Setting the FTP PasswordTo set the FTP password Setting the filepath for the file to be uploadedDisplaying SNTP configuration information SNTP AdministrationSetting the SNTP server address To display SNTP configuration informationEnabling and Setting up SSH Support Enabling and Setting up SSL SupportSSL Technical Specifications SSH Technical SpecificationsSSL Technical Specifications SSL Command SummaryEnabling and Setting up SSL Support To enable or disable SSL supportSSH Technical Specifications SSH Command SummaryEnabling and Setting up SSH Support To enable or disable SSH supportSNMP SNMP Command SummaryEnabling and Setting up SNMP Support To enable SNMP supportSetting the Get/Set community strings To reset the trap destinationTo set the trap timer Setting the Trap community stringTower Status traps SNMP TrapsTrap Summary Infeed Status trapsTemperature/Humidity Sensor Status traps Outlet Status trapsEnvironmental Monitor Status traps Load trapsTemp Trap Temp trapsHumidity traps Humidity TrapEnabling or Disabling a Status trap Configuring Traps SNMP Trap Command SummaryTo Enable or Disable a Status trap To Enable or Disable a Change trap To Enable or Disable a Load trapSetting the Infeed Load limit To Enable or Disable the Temp trapSetting the Humidity sensor threshold limits Setting the Temperature sensor threshold limitsTo Enable or Disable the Humid trap To set the Temperature threshold limitsStatus Displaying trap configuration informationTo display trap information WebServer1U PLOADING F IRMWARE R ESETTING TO F ACTORY D EFAULTS5. Appendices T ECHNICAL S PECIFICATIONSTo reset to factory defaults from the command line Resetting to Factory DefaultsTo reset to factory defaults from the HTML interface To reset to factory defaults using the reset buttonPhysical Specifications Technical SpecificationsPower Ratings Models Europe/AsiaBranch Circuit Protection LED IndicatorsData Connections RS-232 portPage