MGE UPS Systems Switched PDU Connecting Devices, Connecting the Sensors, Connecting to the Unit

Page 9
Connecting Devices

2. Installation

Connecting Devices

To avoid the possibility of noise due to arcing:

1.Keep the device’s on/off switch in the off position until after it is plugged into the outlet, or

log into the user interface and turn the outlets off before connecting the devices to the unit(s). After connecting the devices, turn them on from the user interface.

2.Connect devices to the outlets.

On 230V units, install a retention clip for each outlet; Pull the prongs out slightly and insert them into holes on the sides, then insert the device’s power cord and snap the clip over the cord.

NOTE:

1.MGE UPS SYSTEMS recommends even distribution of attached devices across the all available outlets to avoid exceeding the outlet, quad or octet ratings limitations. See Power Ratings Technical Specifications more information.

2.The outlet retention clips provided with 230V units are designed for use with MGE UPS SYSTEMS’s IEC 60320/C13 to IEC 60320/C14 cable and may not properly fit 3rd party cables.

Always disconnect the power supply cord before opening to avoid electrical shock. Afin d’éviter les chocs électriques, débranchez le cable électrique avant d’ouvrir.

Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.

Connecting the Sensors

The Switched PDU is equipped with two mini RJ11 T/H ports for attachment of the included Temperature/Humidity sensor. Attach the mini RJ11 plug of the sensor(s) to the appropriate T/H port.

Connecting to the Unit

Serial (RS232) port

Switched PDU models are equipped with an RJ45 Serial RS-232 port for attachment to a PC or networked terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F serial port adapter as required. See Data Connections in Technical Specifications for more information on the Serial RS-232 port.

Ethernet port

Switched PDU models are equipped with an RJ45 10/100Base-T Ethernet port for attachment to an existing network. This connection allows access via Telnet, Secure Shell (SSH) or a common web browser.

The unit configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet/SSH or via a web browser:

IP address:

192.168.1.254

Subnet Mask:

255.255.255.0

Gateway:

192.168.1.1

The local PC network connection must be configured as noted below:

NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.

IP address:

192.168.1.x (where x is 2-253)

Subnet Mask:

255.255.255.0

301-0399-4 Rev A. - Page 9

Image 9
Contents E T N I N U E H T Switched PDU Installation and user manualDangerous Voltage InstructionsProtective Grounding Terminal Life-Support PolicyINSTALLATION ContentsGETTING STARTED OPERATIONS1. Getting Started Quick Start Guideuser account prior to attachment to your network 2. Installation Standard AccessoriesAdditional Required Items Figure 1. Unit Views Equipment Overview1 Power Input 2 Input Current LED 3 Ethernet / RS232 Ports 4 Temperature / Humidity PortsInstalling the Power Input Retention Bracket Safety PrecautionsFigure 2. Retention Bracket assembly To install the power input retention bracketTo attach a power cord to the unit Connecting to the Power SourceTo connect to the power source MountingConnecting the Sensors Connecting DevicesConnecting to the Unit Serial RS232 portPage I NTERFACES 3. OperationsHTML I NTERFACE C OMMAND L INE I NTERFACE3. Operations Usernames and PasswordsInterfaces Outlet Naming and GroupingHTML Interface Figure 4. Example HTML page Logging InTo log in by HTML Individual Outlet ControlGroup Outlet State/Control State Field ValuesEnvironmental Monitoring ConfigurationInput Load SensorsTelnet/SSH NetworkHTTP/SSL Setting the IP address, subnet mask or gatewaySetting the HTTP authentication method Serial PortsSetting SSL access level Setting the data-rate for the serial portsGroups OutletsUsers Changing a user passwordAdding and Deleting outlet access Changing a user’s access privilege levelAdding and Deleting group access Adding and Deleting serial port accessSNMP SNTPSetting the filename for upload Testing the FTP upload configurationTools Command Line InterfaceRestart Logging InAdministrative Command Summary Operations Command SummaryAdministrative Command Summary continued To display the names of commands that you may executeRebooting outlets Operations CommandsTo reboot one or more outlets Turning outlets onTo display on/off status of one or more outlets Displaying outlet statusTo display accessible outlets Displaying accessible outletsDisplaying accessible groups To display accessible groupsTo display accessible serial ports Displaying accessible serial portsConnecting to a serial device Displaying infeed statusTo display the status of the Environmental Monitor Displaying the status of the Environmental MonitorStarting a new session To start a new sessionUser Administration Administration CommandsCreating a user account To create a user accountTo change a password Changing a passwordSetting user access level privileges To set the access level privilege for a userTo display user access privilege levels Displaying the access privilege levelsAdding outlet access to a user To grant outlet access to a userTo delete outlet access for a user Deleting outlet access for a userAdding group access to a user To grant group access to a userDisplaying user outlet, group and serial port access Group AdministrationTo display user outlet, group and serial port access Creating a group nameAdding an outlet to a group Outlet AdministrationTo add an outlet to a group Deleting an outlet from a groupTo set the wakeup state Setting the outlet wakeup stateDisplaying outlet information To display outlet informationSetting the serial ports data-rate Serial Port AdministrationEnabling or disabling active signal checking for serial connections To enable or disable active signal checking for serial connectionsDisplaying system configuration information System AdministrationTo display system configuration information Creating a location descriptionTo create a tower name Creating a descriptive tower nameDisplaying tower information To display tower informationTo perform a warm boot TCP/IP AdministrationSetting the IP address Setting the subnet maskDisplaying network configuration information HTTP AdministrationTo display network configuration information To enable or disable HTTP supportFTP Administration Telnet AdministrationTo set the HTTP authentication method To enable or disable Telnet supportTo set the FTP password Setting the FTP PasswordSetting the filename to be uploaded Setting the filepath for the file to be uploadedSetting the SNTP server address SNTP AdministrationDisplaying SNTP configuration information To display SNTP configuration informationSSL Technical Specifications Enabling and Setting up SSL SupportEnabling and Setting up SSH Support SSH Technical SpecificationsEnabling and Setting up SSL Support SSL Command SummarySSL Technical Specifications To enable or disable SSL supportEnabling and Setting up SSH Support SSH Command SummarySSH Technical Specifications To enable or disable SSH supportEnabling and Setting up SNMP Support SNMP Command SummarySNMP To enable SNMP supportTo set the trap timer To reset the trap destinationSetting the Get/Set community strings Setting the Trap community stringTrap Summary SNMP TrapsTower Status traps Infeed Status trapsEnvironmental Monitor Status traps Outlet Status trapsTemperature/Humidity Sensor Status traps Load trapsHumidity traps Temp trapsTemp Trap Humidity TrapConfiguring Traps SNMP Trap Command Summary To Enable or Disable a Status trapEnabling or Disabling a Status trap Setting the Infeed Load limit To Enable or Disable a Load trapTo Enable or Disable a Change trap To Enable or Disable the Temp trapTo Enable or Disable the Humid trap Setting the Temperature sensor threshold limitsSetting the Humidity sensor threshold limits To set the Temperature threshold limitsTo display trap information Displaying trap configuration informationStatus WebServer15. Appendices R ESETTING TO F ACTORY D EFAULTSU PLOADING F IRMWARE T ECHNICAL S PECIFICATIONSTo reset to factory defaults from the HTML interface Resetting to Factory DefaultsTo reset to factory defaults from the command line To reset to factory defaults using the reset buttonPower Ratings Technical SpecificationsPhysical Specifications Models Europe/AsiaData Connections LED IndicatorsBranch Circuit Protection RS-232 portPage