3. Operation

Make sure that the voltages and frequencies of the two sources S1 and S2 are identical.

Make sure that the voltages of the two sources S1 and S2 are the same as the rated voltage (400 V) of Upsilon STS, otherwise see section 3.5 (Customization).

3.1 Start-up

 

 

 

1

 

 

 

2

 

 

 

3

Q1

Q5 Q6

Q2

 

 

1

1

 

 

0

0

4

 

 

 

 

 

6

 

 

 

7

Q1BP

Q3

Q2BP

 

1

1

1

 

0

0

0

 

S1

 

S2

 

 

 

 

29

 

Q1

Q2

30

 

 

 

 

 

31

 

 

 

32

 

 

 

33

Q1BP

Q3

 

Q2BP

 

 

36

 

 

 

 

 

 

37

 

 

 

38

1 - Check that the two sources are energised (voltage present).

2 - Set circuit breakers Q5 2 and Q6 3 to the ON position (position 1).

3 - Turn switch Q1BP 6 to the ON position (position 1). LEDs 37 and 38 go on.

The load is supplied by Source 1 via the bypass.

4 - Set switches Q1 1 and Q3 7 to the ON position (position 1). LEDs 29 , 31 , and 36 go on.

5 - Turn switch Q1BP 6 back to the OFF position (position 0). LED 37 goes off.

6 - Set switch Q2 4 to the ON position (position 1). LEDs 30 and 32 go on.

The load is supplied by Source 1.

If LED 33 is red or off, if LEDs

31and/or 32 are orange or red: see section "Maintenance".

3.2 Shutdown

 

 

1

 

 

2

 

 

3

Q1

Q5 Q6

Q2

 

1

1

 

0

4

 

0

 

 

7

Q1BP

Q3

Q2BP

1

 

1

0

0

0

S1

 

S2

 

Q1

Q2

Q1BP

Q3

Q2BP

1

- Set switches Q1 1 , Q2

4 and Q3

7

to the OFF position (position 0).

 

2

- Set circuit breakers Q5

2 and Q6

3

to the OFF position (position 0).

 

All LEDs should go off.

 

 

The load is not supplied with power.

Dangerous voltage levels are still present inside the Upsilon STS cabinet, in the connection zone.

34020113EN/AA - Page 19

Image 19
Contents Upsilon STS 2 34020113EN/AA Introduction Document Using this documentForeword PictogramsContents Appendix Upsilon STS 30 60 100 160 250 a cabinet 1400 mm high PresentationUpsilon STS 30 60 100 160 250 a cabinet 1400 mm high Access to control and connectionsFunction buttons Man / machine interfaceJBus communication card Relay communication cardOutput terminal block Positioning InstallationPower connections Upsilon STS 30 to 250 a Input Phases + PEN Output L1 L2 L3 Upsilon STS 400 to 600 a Input Phases + PEN Output Connection of the emergency power off terminal block RS485 Connection of the communication cardsConnection of the Jbus communication card RS232Characteristics of the input contacts Characteristics of the output contactsConnection of the relay communication card Shutdown Load is not supplied with powerOperation Start-upManual transfer to the alternate source Normal mode. Operation on preferred source S1Operation on the preferred source Automatic transfer to the alternate sourceManual transfer to an out-of-phase alternate source Main screen Display screensUpsilon STS customization Factory setting CustomizationSignals available on each contact Inputs Factory settingCustomization of the relay communication card Identification of anomalies MaintenanceTransfer to the manual bypass Environment UPS recycling at the end of service lifeAppendix Upsilon STS simplified diagram Simplified diagramsSimplified diagram of an installation Glossary Connections Index