MGE UPS Systems 30A user manual Upsilon STS customization, Factory setting Customization

Page 23

3. Operation

3.5 Upsilon STS customization

1 - Press the menu button 26 .

2 - Select "Setup", then "Customization" using the function buttons 3 - Confirm the order by pressing the function button 23 marked 4 - Enter the password.

23marked ￿ or ￿.

.

The password

Ø

Ø

Ø

is set in the factory.

Select "Setup", then "Password" to personalise the password.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PERSONALIZATION

 

 

 

 

 

Current settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal voltage

400 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overvoltage threshold

 

10%

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage threshold

10%

 

 

 

 

 

 

 

 

 

 

 

 

Nominal frequency

50 Hz

 

 

 

 

Overfrequency threshold

5%

 

 

 

 

 

 

 

 

E

 

 

 

Underfrequency threshold

5%

 

 

 

 

 

 

 

 

S

 

 

 

Phase sync tolerance

15°

 

 

 

 

 

 

 

 

C

 

 

 

Retransfer

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The monitoring parameters must be identical for the two sources. These parameters depend on the tolerances of the connected loads.

 

Factory setting

Customization

 

 

 

Return to preferred source after transfer

Automatic

Manual / Automatic

 

 

 

Nominal source voltage

400 V

380 / 400 / 415 V

 

 

 

Overvoltage threshold

Un +10%

Un +5% to Un +20%

 

 

in 1% steps

 

 

 

Undervoltage threshold

Un -10%

Un -5% to Un -20%

 

 

in 1% steps

 

 

 

Nominal source frequency

50 Hz

50 / 60 Hz

 

 

 

Frequency tolerances

± 5%

+1% to +10%

 

 

-1% to -10%

 

 

in 0.5% steps

 

 

 

Phase error tolerance between the two sources

± 15°

± 1° to ± 45° in 1° steps

 

 

 

34020113EN/AA - Page 23

Image 23
Contents Upsilon STS 2 34020113EN/AA Introduction Document Using this documentForeword PictogramsContents Appendix Upsilon STS 30 60 100 160 250 a cabinet 1400 mm high PresentationUpsilon STS 30 60 100 160 250 a cabinet 1400 mm high Access to control and connectionsFunction buttons Man / machine interfaceOutput terminal block Relay communication cardJBus communication card Positioning InstallationPower connections Upsilon STS 30 to 250 a Input Phases + PEN Output L1 L2 L3 Upsilon STS 400 to 600 a Input Phases + PEN Output Connection of the emergency power off terminal block RS485 Connection of the communication cardsConnection of the Jbus communication card RS232Connection of the relay communication card Characteristics of the output contactsCharacteristics of the input contacts Shutdown Load is not supplied with powerOperation Start-up Manual transfer to the alternate source Normal mode. Operation on preferred source S1 Operation on the preferred source Automatic transfer to the alternate sourceManual transfer to an out-of-phase alternate source Main screen Display screensUpsilon STS customization Factory setting CustomizationCustomization of the relay communication card Inputs Factory settingSignals available on each contact Transfer to the manual bypass MaintenanceIdentification of anomalies Environment UPS recycling at the end of service lifeAppendix Simplified diagram of an installation Simplified diagramsUpsilon STS simplified diagram Glossary Connections Index