MGE UPS Systems 30A Customization of the relay communication card, Inputs Factory setting

Page 24

3. Operation

3.6 Customization of the relay communication card

1.A

1.B

Inputs

Factory setting

-Memorised faults reset command.

-Command to disable transfer.

Signals available on each contact

-Memorised faults reset command.

-Selection command for source S1.

-Selection command for source S2.

-Selection command for the authorised automatic retransfer mode.

-Selection command for the inhibited automatic retransfer mode.

-Command to authorise transfer.

-Command to disable transfer.

-EPO command (enables the opening command for switches Q1 and Q2).

 

Outputs

Factory setting

1.1

 

- Load-supplied status condition (presence or

 

absence of power to the load).

 

 

1.2

 

- General alarm (fault on one of the sources or

 

on the Upsilon STS).

 

 

 

 

 

1.3

 

- Upsilon STS fault.

 

 

 

1.4

 

- Overload status condition.

1.5

 

- Source S1 status condition (active or inactive).

1.6

 

- Source S2 status condition (active or inactive).

 

 

 

Signals available on each contact

-Load-supplied status condition (presence or absence of power to the load).

-General alarm (fault on one of the sources or on the Upsilon STS).

-Upsilon STS fault.

-Source S1 status condition (within or outside tolerances).

-Source S2 status condition (within or outside tolerances).

-Phase-error condition between the two sources (within or outside tolerances).

-Source S1 status condition (active or inactive).

-Source S2 status condition (active or inactive).

-Preferred-source status condition (S1 inactive and S2 active).

-Automatic-transfer status condition (authorised or not).

-Overload status condition.

Page 24 - 34020113EN/AA

Image 24
Contents Upsilon STS 2 34020113EN/AA Introduction Using this document ForewordPictograms DocumentContents Appendix Presentation Upsilon STS 30 60 100 160 250 a cabinet 1400 mm highAccess to control and connections Upsilon STS 30 60 100 160 250 a cabinet 1400 mm highMan / machine interface Function buttonsRelay communication card JBus communication cardOutput terminal block Installation PositioningPower connections Upsilon STS 30 to 250 a Input Phases + PEN Output L1 L2 L3 Upsilon STS 400 to 600 a Input Phases + PEN Output Connection of the emergency power off terminal block Connection of the communication cards Connection of the Jbus communication cardRS232 RS485Characteristics of the output contacts Characteristics of the input contactsConnection of the relay communication card Load is not supplied with power OperationStart-up ShutdownNormal mode. Operation on preferred source S1 Operation on the preferred sourceAutomatic transfer to the alternate source Manual transfer to the alternate sourceManual transfer to an out-of-phase alternate source Display screens Main screenFactory setting Customization Upsilon STS customizationInputs Factory setting Signals available on each contactCustomization of the relay communication card Maintenance Identification of anomaliesTransfer to the manual bypass UPS recycling at the end of service life EnvironmentAppendix Simplified diagrams Upsilon STS simplified diagramSimplified diagram of an installation Glossary Index Connections