3. Operation
3.6 Customization of the relay communication card
1.A
1.B
Inputs
Factory setting
-Memorised faults reset command.
-Command to disable transfer.
Signals available on each contact
-Memorised faults reset command.
-Selection command for source S1.
-Selection command for source S2.
-Selection command for the authorised automatic retransfer mode.
-Selection command for the inhibited automatic retransfer mode.
-Command to authorise transfer.
-Command to disable transfer.
-EPO command (enables the opening command for switches Q1 and Q2).
| Outputs | Factory setting |
1.1 |
| - |
| absence of power to the load). | |
|
| |
1.2 |
| - General alarm (fault on one of the sources or |
| on the Upsilon STS). | |
|
| |
|
|
|
1.3 |
| - Upsilon STS fault. |
|
|
|
1.4 |
| - Overload status condition. |
1.5 |
| - Source S1 status condition (active or inactive). |
1.6 |
| - Source S2 status condition (active or inactive). |
|
|
|
Signals available on each contact
-
-General alarm (fault on one of the sources or on the Upsilon STS).
-Upsilon STS fault.
-Source S1 status condition (within or outside tolerances).
-Source S2 status condition (within or outside tolerances).
-
-Source S1 status condition (active or inactive).
-Source S2 status condition (active or inactive).
-
-
-Overload status condition.
Page 24 - 34020113EN/AA