MGE UPS Systems 30A user manual Appendix

Page 27

6. Appendix

6.1 Technical data Output currents and voltage

Rated output current:

30 A

60 A

100 A

160 A

250 A

400 A

600 A

 

 

 

 

 

 

 

 

 

Input and output voltage:

 

 

 

 

 

 

 

 

Rated operating voltage:

 

 

380 V / 400

V / 415 V

 

 

Maximum voltage:

 

 

498 V (415

V +20%)

 

 

Minimum voltage:

 

 

247 V (380 V -35%)

 

 

Rated frequency:

 

50 or 60 Hz (45 Hz minimum, 66 Hz maximum)

 

 

 

 

 

 

 

 

 

 

Thermal characteristics

Heat losses (1):

 

 

 

 

 

 

 

at rated power:

195 W

295 W

430 W

615 W

920 W

1420 W

2150 W

at 50% rated power:

150 W

195 W

260 W

350 W

495 W

735 W

1070 W

 

 

 

 

 

 

 

 

Required ventilation:

350 m3/h

350 m3/h

350 m3/h

1600 m3/h

1600 m3/h

2300 m3/h

2300 m3/h

 

 

 

 

 

 

 

 

(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.

Noise level

Noise in dB (ISO 3746):

55

55

55

59

59

59

59

Cable sizes

Cross-sectional area in mm2 :

50

50

50

120

120

240

240

Recommended protection devices upstream of Upsilon STS

Type of circuit breaker:

 

 

 

 

 

 

TNS system:

C60L 32A

NS100H 4P 4D

NS160H

NS250H

NS400H

NS630H

 

 

 

4P 4D

4P 4D

4P 4D

4P 4D

TNC system:

 

NS100H 3P

NS160H

NS250H

NS400H

NS630H

 

 

 

3P

3P

3P

3P

 

 

 

 

 

 

 

Trip unit:

curve C

STR22SE

STR22SE

STR22SE

STR23SE

STR23SE

 

 

 

 

 

 

 

Thermal setting:

1.05 In

1.05 In

1.05 In

1.05 In

1,05 In

1.05 In

 

 

 

 

 

 

 

Magnetic setting:

10xIn

10xIn

10xIn

10xIn

10xIn

10xIn

 

 

 

 

 

 

 

Permissible-overload curve

32

In

 

 

 

 

 

16

In

 

 

 

 

 

8

In

 

 

 

 

 

4

In

 

 

 

 

 

2

In

 

 

 

 

 

 

In

 

 

 

 

t(s)

 

0.1 s

1 s

10 s

100 s

1000 s

 

0.01 s

During an overload, transfer between sources is disabled.

Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.

34020113EN/AA - Page 27

Image 27
Contents Upsilon STS 2 34020113EN/AA Introduction Document Using this documentForeword PictogramsContents Appendix Upsilon STS 30 60 100 160 250 a cabinet 1400 mm high PresentationUpsilon STS 30 60 100 160 250 a cabinet 1400 mm high Access to control and connectionsFunction buttons Man / machine interfaceRelay communication card JBus communication cardOutput terminal block Positioning InstallationPower connections Upsilon STS 30 to 250 a Input Phases + PEN Output L1 L2 L3 Upsilon STS 400 to 600 a Input Phases + PEN Output Connection of the emergency power off terminal block RS485 Connection of the communication cardsConnection of the Jbus communication card RS232Characteristics of the output contacts Characteristics of the input contactsConnection of the relay communication card Shutdown Load is not supplied with powerOperation Start-upManual transfer to the alternate source Normal mode. Operation on preferred source S1Operation on the preferred source Automatic transfer to the alternate sourceManual transfer to an out-of-phase alternate source Main screen Display screensUpsilon STS customization Factory setting CustomizationInputs Factory setting Signals available on each contactCustomization of the relay communication card Maintenance Identification of anomaliesTransfer to the manual bypass Environment UPS recycling at the end of service lifeAppendix Simplified diagrams Upsilon STS simplified diagramSimplified diagram of an installation Glossary Connections Index