MGE UPS Systems 30A Maintenance, Identification of anomalies, Transfer to the manual bypass

Page 25

4. Maintenance

4.1 Identification of anomalies

General-alarm

S1 31 or S2 32

Static-switch

Buzzer

System output

Meaning

LED 21

LED

LED 33 or 34

 

LED 38

 

 

-

-

Beeps

-

Internal STS fault.

 

 

 

 

 

Source outside

-

 

-

Beeps

-

tolerances, load still

 

 

 

 

 

 

 

 

supplied.

 

 

 

Beeps

 

Source outside

 

 

 

-

 

-

 

-

 

tolerances, no voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

The load cannot be

 

 

 

 

 

supplied by this source.

 

 

 

Beeps

-

 

-

-

 

 

Static-switch fault.

 

 

 

-

-

-

-

Overload.

-

-

-

-

Load not supplied.

The meaning of all these anomalies are detailed on the display:

Select the alarm: the corresponding informations are displayed.

4.2 Transfer to the manual bypass

Q1

Q5 Q6

Q2

 

 

1

1

4

 

 

 

 

0

0

 

Q1BP

Q3

Q2BP

 

1

1

1

 

0

0

0

 

Q1

Q5 Q6

Q2

 

 

1

1

 

 

0

0

 

 

 

 

6

Q1BP

Q3

Q2BP

 

1

1

1

 

0

0

0

 

Q1

Q5 Q6

Q2

1

 

1

1

 

 

 

0

0

 

 

 

 

7

Q1BP

Q3

Q2BP

 

1

 

1

 

0

0

0

 

Transfer to the manual bypass for source S1:

1 - Manually transfer the load to source S1.

2 - Set switch Q2 4 to the OFF position (position 0).

3 - Set switch Q1BP 6 to the ON position (position 1).

The load is supplied by source S1 via the bypass.

4 - Set switches Q1 1 and Q3 7 to the OFF position (position 0).

The operation for source S2 is identical, using switches Q2 and Q2BP.

Interlocking of the bypass lines is ensured by use of a single key that must be inserted on the bypass switch to be operated.

34020113EN/AA - Page 25

Image 25
Contents Upsilon STS 2 34020113EN/AA Introduction Foreword Using this documentPictograms DocumentContents Appendix Upsilon STS 30 60 100 160 250 a cabinet 1400 mm high PresentationUpsilon STS 30 60 100 160 250 a cabinet 1400 mm high Access to control and connectionsFunction buttons Man / machine interfaceJBus communication card Relay communication cardOutput terminal block Positioning InstallationPower connections Upsilon STS 30 to 250 a Input Phases + PEN Output L1 L2 L3 Upsilon STS 400 to 600 a Input Phases + PEN Output Connection of the emergency power off terminal block Connection of the Jbus communication card Connection of the communication cardsRS232 RS485Characteristics of the input contacts Characteristics of the output contactsConnection of the relay communication card Operation Load is not supplied with powerStart-up ShutdownOperation on the preferred source Normal mode. Operation on preferred source S1Automatic transfer to the alternate source Manual transfer to the alternate sourceManual transfer to an out-of-phase alternate source Main screen Display screensUpsilon STS customization Factory setting CustomizationSignals available on each contact Inputs Factory settingCustomization of the relay communication card Identification of anomalies MaintenanceTransfer to the manual bypass Environment UPS recycling at the end of service lifeAppendix Upsilon STS simplified diagram Simplified diagramsSimplified diagram of an installation Glossary Connections Index