American Power Conversion 10-30 KVA, 200/208 V manual Operation Display Messages/Troubleshooting

Page 24

Operation – Display Messages/Troubleshooting

Display Message

Meaning

Corrective Action

 

 

 

Low-Battery.

The UPS is in battery operation and

Shut down the system and the load

 

the battery charge is low.

equipment or restore incoming volt-

 

Note: Runtime is limited in duration.

age.

 

 

 

Load Is No Longer

The load previously exceeded the

No is corrective action necessary.

Above Alarm Threshold.

alarm threshold and the situation has

 

 

been corrected either because the load

 

 

decreased or the threshold was

 

 

increased.

 

 

 

 

Load Power Is Above

The load has exceeded the user-

Option 1: Use the display interface to

Alarm Limit.

specified load alarm threshold.

raise the alarm threshold.

 

 

Option 2: Reduce the load.

 

 

 

Mains Not Available.

The frequency or voltage is out of

Correct the input voltage to provide

Input Freq/Volt Out of

acceptable range for normal

acceptable voltage or frequency.

Range.

operation.

 

 

 

 

Min Runtime Restored.

The system runtime dropped below

No corrective action is necessary.

 

the configured minimum and has

 

 

been restored. Additional Battery

 

 

Modules were installed, the existing

 

 

Battery Modules were recharged, the

 

 

load was reduced, or the threshold

 

 

was decreased.

 

 

 

 

No Batteries Are

No battery power is available.

Check that batteries are inserted

Connected.

 

properly.

 

 

 

Number of Battery

One or more battery modules were

No corrective action is necessary.

Modules Decreased.

removed.

 

 

 

 

Number of Battery

One or more battery modules were

No corrective action is necessary.

Modules Increased.

added.

 

 

 

 

Replace Batt(s).

One or more Battery Modules need

Refer to the Module Replacement

 

replacement (only applicable with

section for procedures.

 

internal batteries).

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

Option 1: Allow the battery modules

Threshold.

the user-specified minimum runtime

to recharge.

 

alarm threshold. Either the battery

Option 2: If possible, increase the

 

capacity has decreased, or the load

number of battery modules.

 

has increased.

Option 3: Reduce the load.

 

 

Option 4: Decrease the alarm

 

 

threshold.

 

 

Contact APC Customer Support.

 

 

See back cover.

 

 

 

Site Wiring Fault.

Wrong phase rotation on the input

An electrician should check that the

 

side. The UPS will continue to supply

UPS has been wired properly.

 

conditioned power, but bypass is

 

 

unavailable.

 

 

 

 

16

Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 990-2359A

Image 24
Contents Operation Page Smart-UPSVT and XR Battery Enclosure10-30 kVA 200/208 Page Contents Appendix Options Page General Safety Instructions Symbols used in this guideEnvironmental symbols General safetySafety General Safety Instructions Operation IntroductionSmart-UPS VT Family Range 352mm Enclosures523mm Enclosures Operation Modes Display IntroductionNavigation StatusBasic display navigation principles Control functionsSelect YES, Turn Load Off Status viewsClock set-up DateTime LoggingAlarm threshold Display setupFrom the Display Setup Menu, select Contrast Diagnostics screenMain Menu Display Messages/Troubleshooting Display messagesOperation Display Messages/Troubleshooting Display Message Meaning Corrective Action Front Panel removal Remove Battery Compartment Cover Battery Compartment Cover installation Front Panel installation Total-Power-Off Procedure Restart Procedure Power applicationVoltage confirmation EnterMechanical Bypass Mechanical Bypass LeverTurn into mechanical bypass Page Network Management Card replacement Network Management Card with Environmental MonitorBattery Replacement General safety prior to module replacementBattery Module Removal and installation of Battery Lock if applicable Battery Module removal How to install a Battery Module  How to Obtain Replacement Parts Orderable partsAppendix UPS Components and OptionsSerial number Type labelPart number coding 24kgStabilizing Bracket User interface Foot print Extended Run Battery Enclosure XR Battery Enclosure OptionsPart numbers for XR Battery Enclosures Part number for Battery ModuleAppendix Options Appendix Options Page 990-2359A