Operation – Navigation

To change the language, select Language, and press ENTER. The Language line is now active. Use the UP/DOWN arrows to select the desired language. Press ENTER to confirm your selection.

Contrast setting.

From the Display Setup Menu, select Contrast.

To change the contrast, select Contrast, and press ENTER. Use the UP/DOWN arrows to select the contrast level - the lower the number, the darker the contrast. Select ENTER to confirm the setting.

Beeper setup.

Beeper setup

Beep at: PwrFail+30

Vol: Low

Key Click: Off

Beeper Setup Menu

From the Beeper Setup Menu, select Beeper Setup.

To change the beeper setup, select Beep at and press ENTER. You now have the following options:

Never: If you select this setting, the Beeper will be active at internal UPS errors only.

PwrFail+30: If you select this setting, the Beeper will be active at Internal UPS errors and at main or bypass errors. The Beeper will only sound if the fault has been present for more than 30 seconds.

PwrFail: If you select this setting, the Beeper will be active at Internal UPS errors and at main or bypass errors. The Beeper will sound immediately the error is occurring.

Low Batt: If you select this setting, the Beeper will be active at internal UPS errors and at main or bypass errors and at power failures and at low battery level (if the UPS runs in battery operation). Press ENTER to confirm your setting, or ESC to cancel.

Vol:

The default setting is low. This setting can be changed to medium, high, or Off. Press ENTER to confirm your setting, or ESC to cancel.

Key Click:

The default Key Click function is set to Off. Select On if you want to change this setting to On. Press ENTER to confirm your setting, or ESC to cancel. Press ESC to return to previous screen.

Diagnostics screen

From the Diags screen on the Main Menu, you can view the information given on failures for use in troubleshooting.

990-2359A Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide

13

Image 21
Contents Operation Page Smart-UPSVT and XR Battery Enclosure10-30 kVA 200/208 Page Contents Appendix Options Page Symbols used in this guide General Safety InstructionsEnvironmental symbols General safetySafety General Safety Instructions Introduction OperationSmart-UPS VT Family Range 352mm Enclosures523mm Enclosures Operation Modes Introduction DisplayStatus NavigationControl functions Basic display navigation principlesStatus views Select YES, Turn Load OffDate Clock set-upLogging TimeDisplay setup Alarm thresholdDiagnostics screen From the Display Setup Menu, select ContrastMain Menu Display messages Display Messages/TroubleshootingOperation Display Messages/Troubleshooting Display Message Meaning Corrective Action Front Panel removal Remove Battery Compartment Cover Battery Compartment Cover installation Front Panel installation Total-Power-Off Procedure Power application Restart ProcedureEnter Voltage confirmationMechanical Bypass Mechanical Bypass LeverTurn into mechanical bypass Page Network Management Card with Environmental Monitor Network Management Card replacementBattery Replacement General safety prior to module replacementBattery Module Removal and installation of Battery Lock if applicable How to install a Battery Module Battery Module removal  Orderable parts How to Obtain Replacement PartsUPS Components and Options AppendixType label Serial number24kg Part number codingStabilizing Bracket User interface Foot print Options Extended Run Battery Enclosure XR Battery EnclosurePart number for Battery Module Part numbers for XR Battery EnclosuresAppendix Options Appendix Options Page 990-2359A