Total-Power-Off Procedure

WARNING!

Risk of electric shock – parts inside the UPS and XR Batterty Enclosure are energized from the battery supply even when the AC power is disconnected. Before electrical installation begins, follow the Total-Power-Off procedure to completely de-energize the system.

UPS

Utility/ Mains breaker

XR Battery Enclosure

Set the DC disconnect switch on the XR Enclosure (if available) to the OFF position.

Remove all batteries from the system, or, alternatively, pull out all batteries to the red disconnect line shown on the battery. To ensure sufficient stability, do not pull batteries out beyond the red disconnect line unless completely removing them from the Enclosure.

Set the utility breaker to the OFF or LOCKED-OUT position. If the UPS has dual mains supply, set both supplies to the OFF or LOCKED-OUT position.

WARNING!

Correct lock-out procedures at utility breaker must be followed. If necessary, install a padlock.

22

Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 990-2359A

Image 30
Contents Operation Page Smart-UPSVT and XR Battery Enclosure10-30 kVA 200/208 Page Contents Appendix Options Page Environmental symbols General Safety InstructionsSymbols used in this guide General safetySafety General Safety Instructions Operation IntroductionSmart-UPS VT Family Range 352mm Enclosures523mm Enclosures Operation Modes Display IntroductionNavigation StatusBasic display navigation principles Control functionsSelect YES, Turn Load Off Status viewsClock set-up DateTime LoggingAlarm threshold Display setupFrom the Display Setup Menu, select Contrast Diagnostics screenMain Menu Display Messages/Troubleshooting Display messagesOperation Display Messages/Troubleshooting Display Message Meaning Corrective Action Front Panel removal Remove Battery Compartment Cover Battery Compartment Cover installation Front Panel installation Total-Power-Off Procedure Restart Procedure Power applicationVoltage confirmation EnterMechanical Bypass Mechanical Bypass LeverTurn into mechanical bypass Page Network Management Card replacement Network Management Card with Environmental MonitorBattery Replacement General safety prior to module replacementBattery Module Removal and installation of Battery Lock if applicable Battery Module removal How to install a Battery Module  How to Obtain Replacement Parts Orderable partsAppendix UPS Components and OptionsSerial number Type labelPart number coding 24kgStabilizing Bracket User interface Foot print Extended Run Battery Enclosure XR Battery Enclosure OptionsPart numbers for XR Battery Enclosures Part number for Battery ModuleAppendix Options Appendix Options Page 990-2359A