Battery Replacement
General safety prior to module replacement
WARNING!
• Only trained personnel familiar with the operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.
•The UPS and Battery Enclosure contain an internal energy source. Hazardous voltage may be present even when disconnected from the power source. Follow Total Power Off Procedure to completely
•Never replace batteries when the UPS is running in battery mode!
•Risk of Energy Hazard, 96 V, 7.2
•Batteries do not contain serviceable parts. Do not open.
•Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. Do not dispose of batteries in a fire, as they may explode.
•To ensure continuous battery
•For configurations that include
Two people to lift a component weighing between 18 – 32 kg.
Battery Module
One Battery Module consists of 4 Battery Units (max. 2 Battery Modules shipped in the Enclosures).
4 x 23kg