American Power Conversion 200/208 V Mechanical Bypass Lever, Turn into mechanical bypass

Page 33

Mechanical Bypass

Start-up is included with the UPS, and the start-up procedure described here is only applicable if the UPS requires a subsequent start-up.

Mechanical Bypass Lever

For increased availability, the UPS is equipped with an internal mechanical bypass system providing mains power directly to the output, bypassing all UPS electronics.

CAUTION!

The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.

Turn into mechanical bypass

NOTE!

If the UPS is running and controllable through the display, carry out steps 1 through 6. If not, go directly to step 4.

Control

Display

Status

Diags

Setup

Help

Logging

 

Main Menu

From the Main Menu, select Control and press ENTER

Use UP/DOWN key to navigate to UPS into Bypass and press ENTER

Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER

Remove UPS Front Panel

SEE!

“Front Panel removal” on page 18.

990-2359A Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide

25

Image 33
Contents Operation Page Smart-UPSVT and XR Battery Enclosure10-30 kVA 200/208 Page Contents Appendix Options Page Symbols used in this guide General Safety InstructionsEnvironmental symbols General safetySafety General Safety Instructions Introduction OperationSmart-UPS VT Family Range 352mm Enclosures523mm Enclosures Operation Modes Introduction DisplayStatus NavigationControl functions Basic display navigation principlesStatus views Select YES, Turn Load OffDate Clock set-upLogging TimeDisplay setup Alarm thresholdDiagnostics screen From the Display Setup Menu, select ContrastMain Menu Display messages Display Messages/TroubleshootingOperation Display Messages/Troubleshooting Display Message Meaning Corrective Action Front Panel removal Remove Battery Compartment Cover Battery Compartment Cover installation Front Panel installation Total-Power-Off Procedure Power application Restart ProcedureEnter Voltage confirmationMechanical Bypass Mechanical Bypass LeverTurn into mechanical bypass Page Network Management Card with Environmental Monitor Network Management Card replacementBattery Replacement General safety prior to module replacementBattery Module Removal and installation of Battery Lock if applicable How to install a Battery Module Battery Module removal  Orderable parts How to Obtain Replacement PartsUPS Components and Options AppendixType label Serial number24kg Part number codingStabilizing Bracket User interface Foot print Options Extended Run Battery Enclosure XR Battery EnclosurePart number for Battery Module Part numbers for XR Battery EnclosuresAppendix Options Appendix Options Page 990-2359A