Specifications
SU041,
Item |
| Specification | ||
|
|
|
| |
Power |
|
|
| |
|
|
| ||
Nominal input voltage | 120 VAC |
| ||
|
|
| ||
Input voltage range | 0 – 165 VAC |
| ||
|
|
| ||
Frequency range | 47 – 63 Hz |
| ||
|
| |||
Normal sensitivity transfer times | 8 ms maximum at 60 Hz | |||
10 ms maximum at 50 Hz | ||||
| ||||
|
| |||
Reduced sensitivity transfer | 16 ms maximum at 60 Hz | |||
times | 20 ms maximum at 50 Hz | |||
|
| |||
Maximum current draw | 12 A (SU041 model) | |||
24 A (SU042 models) | ||||
| ||||
|
|
|
| |
Physical |
|
|
| |
|
|
|
| |
Size: | 1.75 × | 17.0 × | 7.5 in | |
4.45 × | 43.2 × | 19 cm | ||
| ||||
|
|
| ||
Net weight | 10 lb (4.5 kg) |
| ||
|
|
| ||
Shipping weight | 15 lb (6.8 kg) |
| ||
|
|
|
| |
Environmental |
|
|
| |
|
|
|
| |
Elevation (above MSL): |
|
|
| |
• Operating | 0 to 10,000 ft (0 to 3000 m) | |||
• Storage | 0 to 50,000 ft (0 to 1500 m) | |||
|
|
|
| |
Temperature: |
|
|
| |
• Operating | 32° to 122° F (0 to 50° C) | |||
• Storage | 5° to 122° F (– 15° to 50° C) | |||
|
|
|
| |
Relative Humidity |
|
|
| |
(Operating and Storage) | 0 to 95%, | |||
|
|
|
|
Approvals/Standards
UL, CSA, FCC Class A
20 | APC Redundant Switch: Installation and Operation Manual |