American Power Conversion Redundant Switch operation manual

Page 20

Operation

 

Emergency

You can use a remotely operated Emergency Power Off (EPO)

Power Off

switch to turn off the UPS and disconnect power to the

 

equipment load. When you turn off the UPS through the

 

Emergency Power Off system, it will turn off immediately

 

without switching to battery operation.

Electrical Hazard

Use only a licensed electrician to perform the following procedure to connect the Redundant Switch and its attached UPSs to your Emergency Power Off system.

1.Use the EPO connector.

2.Use a normally-open contact to connect the +24 terminal to the IN terminal.

3.Wire the external blue four-pin female connector to the emergency power off system.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits.

The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay

Caution

properly isolated from the utility. To avoid

 

 

damage to the Redundant Switch, do not connect

 

the EPO interface to any circuit other than a

 

closure type circuit.

16

APC Redundant Switch: Installation and Operation Manual

Image 20
Contents Redundant Switch APCThis manual is available in English on the enclosed CD Contents Page Before You Begin Pre-Installation Procedures Part Number Description QuantityAvailable Models Voltage Source Input Load OutputModel SU043 SU042-4Do not remove this device Model SU045-1Installation Following example shows how to attach the bracket for See Appendix a Rack-Mount Supplement Installation To the front of the Redundant Switch, connect Use two people to lift the Redundant Switch Turn on the equipment and Redundant Switch Configuration Both UPSs must be the same sine-wave modelRestart the computer on which PowerChute plus is Operation Function LED Display DescriptionYou can use a remotely operated Emergency Power Off EPO LED Display Status of Source Function Select LED Indicator. The three green FunctionFunction Status LED Indicator. The green Function Status Troubleshooting Problem Possible Cause Corrective ActionsContinuously for capability to carry a load and ability to Specifications SpecificationSU043 and SU044-1 SU045 Appendix a Rack-Mount Supplement Type of Rack Hole Type Hardware Required Warranty and Service Except as provided herein, APC makes no warrantiesExpress or implied, including warranties of merchantability Fitness for a particular purpose. Some jurisdictions doWarranty and Service Life-Support Policy Page Radio Frequency Interference APC Worldwide Customer Support USA