Specifications

Item

 

Specification

 

 

 

 

Power

 

 

 

 

 

 

Nominal input voltage

230 VAC

 

 

 

 

Input voltage range

0 325 VAC

 

 

 

 

Frequency range

47 63 Hz

 

 

 

Normal sensitivity

4 ms typical, 8 ms maximum at 60 Hz

transfer times

5 ms typical, 10 ms maximum at 50 Hz

 

 

Reduced sensitivity

8 ms typical, 16 ms maximum at 60 Hz

transfer times

10 ms typical, 20 ms maximum at 50 Hz

 

 

Maximum current

6 A (SU043 model)

draw

13 A (SU044-1 model)

 

 

 

 

Physical

 

 

 

 

 

 

 

Size:

1.75 ×

17.0 ×

7.5 in

4.45 ×

43.2 ×

19 cm

 

 

 

 

Net weight

10 lb (4.5 kg)

 

 

 

 

Shipping weight

15 lb (6.8 kg)

 

 

 

 

 

Environmental

 

 

 

 

 

 

 

Elevation (above

 

 

 

MSL):

0 to 10,000 ft (0 to 3000 m)

• Operating

0 to 50,000 ft (0 to 1500 m)

• Storage

 

 

 

 

 

 

 

Temperature:

 

 

 

• Operating

32° to 122° F (0 to 50° C)

• Storage

5° to 122° F (– 15° to 50° C)

 

 

 

 

Relative Humidity

 

 

 

(Operating and

0 to 95%, non-condensing

Storage)

 

 

 

 

 

 

 

Approvals/Standards

 

 

 

 

 

 

CE, VDE, EN55022, EN55024

 

 

 

 

 

 

APC Redundant Switch: Installation and Operation Manual

21

Image 25
Contents APC Redundant SwitchThis manual is available in English on the enclosed CD Contents Page Before You Begin Part Number Description Quantity Pre-Installation ProceduresVoltage Source Input Load Output Available ModelsModel SU043 Model SU045-1 SU042-4Do not remove this deviceInstallation Following example shows how to attach the bracket for See Appendix a Rack-Mount Supplement Installation To the front of the Redundant Switch, connect Use two people to lift the Redundant Switch Turn on the equipment and Redundant Switch Both UPSs must be the same sine-wave model ConfigurationRestart the computer on which PowerChute plus is Function LED Display Description OperationYou can use a remotely operated Emergency Power Off EPO Function Status LED Indicator. The green Function Status Function Select LED Indicator. The three green FunctionLED Display Status of Source Problem Possible Cause Corrective Actions TroubleshootingContinuously for capability to carry a load and ability to Specification SpecificationsSU043 and SU044-1 SU045 Appendix a Rack-Mount Supplement Type of Rack Hole Type Hardware Required Except as provided herein, APC makes no warranties Warranty and ServiceExpress or implied, including warranties of merchantability Fitness for a particular purpose. Some jurisdictions doWarranty and Service Life-Support Policy Page Radio Frequency Interference USA APC Worldwide Customer Support