Wiring Specifications
Adhere to national and local electrical codes when wiring.
| Input Connections |
|
| Output Connections |
| |
Main Input |
|
|
| Hardwire |
|
|
|
|
| ||||
|
| |||||
Bypass Input (optional) |
|
|
|
|
| |
|
| XL battery pack PDU to UPS: Wire L1, N, |
| |||
|
|
|
|
| ||
|
|
|
| |||
System | Wiring | Number | Voltage | Current | External Input | Wire Size |
|
| of Phases |
| Full Load | Circuit Breaker | (typical)* |
|
|
|
| (maximum | (typical) |
|
SURT15000XLI/ | Input | 1 | 220/230/ | 83 A | 100 A / | 25/35 mm2 |
XLICH |
|
| 240 Vac |
|
| (2/1 AWG) |
| Input | 3 | 380/400/ | 28 A / phase | 35 A / | 6 mm2 |
|
|
| 415 Vac |
|
| (8 AWG) |
| Output | 1 | 220/230/ | 65 A | not required | 25 mm2 |
|
|
| 240 Vac |
|
| (2 AWG) |
| Output | 3 | 380/400/ | 22 A / phase | not required | 6 mm2 |
|
|
| 415 Vac |
|
| (8 AWG) |
SURT20000XLI/ | Input | 1 | 220/230/ | 105 A | 125 A / | 35/50 mm2 |
XLICH |
|
| 240 Vac |
|
| (1/0 AWG) |
| Input | 3 | 380/400/ | 35 A / phase | 50 A / | 10 mm2 |
|
|
| 415 Vac |
|
| (6 AWG) |
| Output | 1 | 220/230/ | 87 A | not required | 35 mm2 |
|
|
| 240 Vac |
|
| (1 AWG) |
| Output | 3 | 380/400/ | 29 A / phase | not required | 10 mm2 |
|
|
| 415 Vac |
|
| (6 AWG) |
*Terminal screw tightening torque: 40
The output frequency is user selectable. Refer to the PowerView display menu screens for available options.