American Power Conversion RT XLI/XLICH user manual Emergency Power Off EPO, Connector

Page 26

Emergency Power Off (EPO)

The output power can be disabled in an emergency by closing a switch connected to the EPO.

Adhere to national and local electrical codes when wiring.

The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by 12 V internal supply. In closed condition, 2 mA of current are drawn.

The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.

The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).

EPO PORT

EPO

(located on rear panel)

Connector

 

Strip the insulation from one end of each wire to be used for

 

connecting the EPO.

 

Insert a screwdriver into the slot above the terminal to be wired.

 

Insert the stripped wire into the terminal. Remove the screwdriver to

 

secure the wire in the terminal. Repeat for each terminal.

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.

22

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Image 26
Contents XLI/XLICH Page Contents Page Unpack package contents About this UPSPhysical Specifications SpecificationsEnvironmental Specifications Maximum Number of XLBPs Supported by the Smart-UPS XLInstallation Stack or rack-mount front panelStack configuration Rack-mount configurationInstall units in rack Install and connect battery modulesRoute ethernet cable and install bezels Accessories Optional accessoriesInstall the wiring trays, refer to graphics below Install input and output wiring trays in UPS rear panel XlbpWiring Specifications Adhere to national and local electrical codes when wiringInput wiring options Input/Output Jumper ConfigurationsSingle phase input, single phase output, single feed Single phase input, single phase output, dual feedThree phase input, single phase output, dual feed Three phase input, single phase output, single feedThree phase input, three phase output, single feed Three phase input, three phase output, dual feedOutput wiring options L3 L2 L1 OSJSingle phase output connection to battery pack PDU PowerView Interface Display OperationNavigating menu screens Main Menu ScreenMenu Tree Navigating sub menu screensSub menu screens SystemExternal Battery Pack Communication Ports Connect power to UPS and loadConnect load to UPS Emergency Power Off EPO ConnectorTroubleshooting Display Messages Output Jumper Configurations tablePage Refer to Contact Information in this Option 2 Correct bypass input Service Maintenance, Transport, and ServiceReplace battery modules Two-Year Warranty Terms of warrantyRegulatory Agency Approvals and Radio Frequency Warnings ModelsDate of product declaration