American Power Conversion RT XLI/XLICH user manual Refer to Contact Information in this

Page 29

Condition

PowerView Display

Reason for Message

Corrective Action

Message

 

 

 

 

 

 

 

General

Need Bat Replacement.

One or more battery pairs are in need

Refer to battery installation

Fault

 

of replacement.

procedure.

 

 

 

 

 

No Batteries Are

No battery power is available.

Check that batteries are installed and

 

Connected.

 

connected properly.

 

 

 

 

 

Discharged Battery.

The UPS is on battery operation and

Shut down the system and the load

 

 

the battery charge is low.

or restore the incoming voltage.

 

 

 

 

 

Low- Battery.

The UPS is on battery operation and

 

 

 

the battery charge is low.

 

 

 

 

 

 

Weak Batt(s) Detected.

One or more weak battery pairs

Replace the weak battery pairs.

 

Reduced Runtime.

detected (only applicable for internal

 

 

 

battery modules).

 

 

 

 

 

 

Batt Temperature Exceeded

The temperature of one or more

Contact APC Customer Support.

 

Upper Limit.

battery packs has exceeded system

Refer to Contact Information in this

 

 

specifications.

manual.

 

 

 

 

 

Battery Over-Voltage

The battery voltage is too high and the

 

 

Warning.

charger has been deactivated.

 

 

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

Option 1) Allow the batteries to

 

Threshold.

the user-specified minimum runtime

recharge.

 

 

alarm threshold. Either the battery

Option 2) If possible, increase the

 

 

capacity has decreased, or the load has

number of battery modules.

 

 

increased.

Option 3) Reduce the load.

 

 

 

 

 

 

Option 4) Decrease the alarm

 

 

 

threshold.

 

 

 

 

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

25

Image 29
Contents XLI/XLICH Page Contents Page About this UPS Unpack package contentsEnvironmental Specifications SpecificationsPhysical Specifications Maximum Number of XLBPs Supported by the Smart-UPS XLStack or rack-mount front panel InstallationRack-mount configuration Stack configurationInstall and connect battery modules Install units in rackRoute ethernet cable and install bezels Optional accessories AccessoriesInstall the wiring trays, refer to graphics below Xlbp Install input and output wiring trays in UPS rear panelAdhere to national and local electrical codes when wiring Wiring SpecificationsInput/Output Jumper Configurations Input wiring optionsSingle phase input, single phase output, dual feed Single phase input, single phase output, single feedThree phase input, three phase output, single feed Three phase input, single phase output, single feedThree phase input, single phase output, dual feed Three phase input, three phase output, dual feedL3 L2 L1 OSJ Output wiring optionsSingle phase output connection to battery pack PDU Operation PowerView Interface DisplayMain Menu Screen Navigating menu screensNavigating sub menu screens Menu TreeSystem Sub menu screensExternal Battery Pack Communication Ports Connect power to UPS and loadConnect load to UPS Connector Emergency Power Off EPOOutput Jumper Configurations table Troubleshooting Display MessagesPage Refer to Contact Information in this Option 2 Correct bypass input Service Maintenance, Transport, and ServiceReplace battery modules Terms of warranty Two-Year WarrantyModels Regulatory Agency Approvals and Radio Frequency WarningsDate of product declaration