APC ACRP101, ACRP501, ACRP500, ACRP100, ACRD500 Setpoints, Dehumid Deadband 2.0-10.0%, Configuration

Page 27

Setpoints

Assign the following group setpoints and then click Apply. The setpoints for each mode must be within the following ranges:

Cool: 64.4–77.0°F (18.0–25.0°C)

Supply Air: 62.6–73.4°F (17.0–23.0°C)

The following setpoints apply to the ACRP100 and ACRP500 cooling units:

Dehumidify: 35.0–60.0% RH

Dehumid Deadband: 2.0–10.0%

Humidify: 25.0–50.0% RH

Reheat: 50.0–64.4°F (10.0–18.0°C)

For ACRP100 and ACRP500 cooling units: The Supply Air setpoint must be at least 2.0°F (1.1°C) above the Reheat setpoint. The Dehumidify setpoint must be at least 5% above the Humidify setpoint. If the Supply Air setpoint is greater than the Cool setpoint, the cooling unit activates an alarm and resets the Supply Air setpoint to equal the Cool setpoint.

Configuration

Number of units in group. Enter the number of units in the group, then click Apply. Up to twelve units can be configured to work as a group.

Configuration type. Select the configuration type, which is the air flow control strategy the group uses, then click Apply:

RACS—Rack Air Containment System. Air flow in the enclosure is controlled by a ducting system fitted to the enclosure.

HACS—Hot Aisle Containment System. Air flow in the room is controlled by enclosing the hot air aisle.

In-Row—Air flow is horizontal, to allow in-row operation of the cooling group.

Percent glycol. Enter the percentage of glycol the group uses to cool the environment. This information is used to calculate the amount of energy (in kW) required by the unit. Percent glycol applies only to ACRC500 and ACRP500 cooling units. Only a qualified service technician should change the amount of glycol in the group.

PID control settings. For ACRP100 and ACRP500 cooling units. The Proportional + Integral + Derivative (PID) control loop is used to control the output of the group. Enter the settings for the Cool and Reheat PIDs, and the Humidify Sensitivity Band, then click Apply.

Note: The loops must be tuned after the room load is in place, and then periodically if the room load changes. Only a qualified service technician should perform PID tuning.

For more information about PID tuning, see the Operation and Maintenance manual for your cooling unit, available on the Utility CD or on the APC Web site, www.apc.com.

InRow RC/RD/RP (600 mm) User’s Guide

19

Image 27 Contents
User’s Guide Page Contents Web Interface Administration Security Administration Notification Verifying Upgrades and Updates Page Product Description Features of the InRow RC/RD/RP 600 mm cooling unitInitial setup IntroductionInternal Management Features Access priority for logging onOverview Types of user accounts How to Recover from a Lost Password Display Interface LEDs Watchdog FeaturesHow to Log On Remote access to the control consoleControl Console Local access to the control console Example main screen Main ScreenInformation and status fields Main screen status fields Device Manager option Control Console MenusMenu structure Main menuControl Administrator and Device Manager access Network optionSystem option Web Interface Supported Web browsersURL address formats Error Message Browser Cause of the Error Common browser error messages at log onHelp SummaryNavigation tabs Quick statusSelect a tab to perform a task InRow RC/RD/RP 600 mm User’s Guide Group Alarm statusCooling Unit Operation HomeConfiguration SetpointsDehumid Deadband 2.0-10.0% Detailed status UnitCompressor drive status ACRD500 and ACRP100 cooling units IdentificationRun hours Thresholds Service intervalsAir Filter-18 weeks Humidifier-26 weeks Condensate Pump-52 weeksConfiguration Reverse lookup LogsEvents LogData GraphingInterval Hours specified as Delay hours between Uploads RotationParameter Description Setting Definition SyslogServers Settings Test How to use FTP or SCP to retrieve the log files Queries Modbus requests and Snmp GETs Permission levels Administration SecuritySetting user access Local UsersRemote Users AuthenticationInRow RC/RD/RP 600 mm User’s Guide Summary of the configuration procedure Configuring the Radius ServerInactivity Timeout Configuring a Radius server on UNIX, with shadow passwordsSupported Radius servers Setting Administration NetworkTCP/IP and communication settings TCP/IP settingsDhcp Configuration page1Boot mode transition. Tag 2, Len 1, Data 1/2 Dhcp response optionsAPC cookie. Tag 1, Len 4, Data 1APC Port speed Query Type Selected Query Question to Use DNS AdminstrationNetworkDNSserversEnabled WebOption Description Status On this link to view the certificate’s contentsAES ConsoleIs loaded Snmp Option Description Related Topics FTP serverTypes of notification Administration NotificationConfiguring event actions Event ActionsInRow RC/RD/RP 600 mm User’s Guide InRow RC/RD/RP 600 mm User’s Guide Mail notification Active, Automatic, Direct NotificationSmtp Setting DescriptionSnmp traps Administration General Options Information about the Cooling UnitDate & time Action Definition User configuration file iniReset the interface Unit preferenceQuick links Serial ModbusAbout Installation APC Device IP Configuration WizardCapabilities, Requirements, and Installation Use the Wizard to configure basic TCP/IP settingsSelect Remotely over the network, and click Next Configure the basic TCP/IP settings remotelyUse the Wizard Launch the WizardSelect Locally through the serial port, and click Next Configure or reconfigure the TCP/IP settings locallyRetrieving and Exporting the .ini File How to Export Configuration SettingsSummary of the procedure Contents of the .ini fileDetailed procedures Exporting the file to multiple cooling units. T Event text Description Upload Event and Error MessagesEvent and its error messages Errors generated by overridden valuesFirmware files How to Upgrade FirmwareFile Transfers Benefits of upgrading firmwareFirmware file transfer methods Ftp put apchw03aosxxx.bin Use FTP or SCP to upgrade one cooling unit\cd\apc Ftp open 150.250.6.10Use Xmodem to upgrade one cooling unit Upgrade multiple cooling unitsInRow RC/RD/RP 600 mm User’s Guide Verifying Upgrades and Updates Last transfer result codesCode Description Page Page 2009 990-2937A