APC ACRD501, ACRP501, ACRP500, ACRP100, ACRP101 Configure or reconfigure the TCP/IP settings locally

Page 69

Configure or reconfigure the TCP/IP settings locally

To configure a single cooling unit through a serial connection:

1.Contact your network administrator to obtain valid TCP/IP settings.

2.Connect the provided serial configuration cable from an available communications port on your computer to the serial port of the cooling unit. Make sure no other device is using the computer port.

3.From the Start menu, launch the Wizard application.

a.If the cooling unit is not configured, wait for the Wizard to detect it.

b.If you are assigning basic TCP/IP settings serially to a cooling unit, click Next>.

4.Select Locally (through the serial port), and click Next >.

5.Enter the TCP/IP settings (System IP, Subnet Mask, and Default Gateway) for the cooling unit. Then click Next >.

6.On the Transmit Current Settings Locally screen, if you select Start a Web browser when finished, the default Web browser connects to the cooling unit after the Wizard transmits the settings.

7.Switch the main breaker on the front of the electrical panel to OFF. Wait one second. Switch the main breaker to ON.

Note: If you wait too long to return power to the cooling unit, you must repeat step 7.

If the IP address you entered is in use on the network, the Wizard prompts you to enter an IP address that is not in use. Enter a correct IP address, and click Finish.

8.If you selected Start a Web browser when finished in step 6, you can now configure other parameters through the Web interface of the cooling unit.

InRow RC/RD/RP (600 mm) User’s Guide

61

Image 69 Contents
User’s Guide Page Contents Web Interface Administration Security Administration Notification Verifying Upgrades and Updates Page Initial setup Features of the InRow RC/RD/RP 600 mm cooling unitIntroduction Product DescriptionInternal Management Features Access priority for logging onOverview Types of user accounts How to Recover from a Lost Password Display Interface LEDs Watchdog FeaturesHow to Log On Remote access to the control consoleControl Console Local access to the control console Example main screen Main ScreenInformation and status fields Main screen status fields Menu structure Control Console MenusMain menu Device Manager optionControl Administrator and Device Manager access Network optionSystem option Web Interface Supported Web browsersURL address formats Error Message Browser Cause of the Error Common browser error messages at log onNavigation tabs SummaryQuick status HelpSelect a tab to perform a task InRow RC/RD/RP 600 mm User’s Guide Cooling Unit Operation Alarm statusHome GroupConfiguration SetpointsDehumid Deadband 2.0-10.0% Detailed status UnitCompressor drive status ACRD500 and ACRP100 cooling units IdentificationRun hours Air Filter-18 weeks Humidifier-26 weeks Service intervalsCondensate Pump-52 weeks ThresholdsConfiguration Events LogsLog Reverse lookupData GraphingInterval Hours specified as Delay hours between Uploads RotationParameter Description Setting Definition SyslogServers Settings Test How to use FTP or SCP to retrieve the log files Queries Modbus requests and Snmp GETs Setting user access Administration SecurityLocal Users Permission levelsRemote Users AuthenticationInRow RC/RD/RP 600 mm User’s Guide Summary of the configuration procedure Configuring the Radius ServerInactivity Timeout Configuring a Radius server on UNIX, with shadow passwordsSupported Radius servers TCP/IP and communication settings Administration NetworkTCP/IP settings SettingDhcp Configuration page1Boot mode transition. Tag 2, Len 1, Data 1/2 Dhcp response optionsAPC cookie. Tag 1, Len 4, Data 1APC Port speed Query Type Selected Query Question to Use DNS AdminstrationNetworkDNSserversEnabled WebOption Description Status On this link to view the certificate’s contentsAES ConsoleIs loaded Snmp Option Description Related Topics FTP serverConfiguring event actions Administration NotificationEvent Actions Types of notificationInRow RC/RD/RP 600 mm User’s Guide InRow RC/RD/RP 600 mm User’s Guide Mail notification Active, Automatic, Direct NotificationSmtp Setting DescriptionSnmp traps Administration General Options Information about the Cooling UnitDate & time Reset the interface User configuration file iniUnit preference Action DefinitionQuick links Serial ModbusAbout Capabilities, Requirements, and Installation APC Device IP Configuration WizardUse the Wizard to configure basic TCP/IP settings InstallationUse the Wizard Configure the basic TCP/IP settings remotelyLaunch the Wizard Select Remotely over the network, and click NextSelect Locally through the serial port, and click Next Configure or reconfigure the TCP/IP settings locallySummary of the procedure How to Export Configuration SettingsContents of the .ini file Retrieving and Exporting the .ini FileDetailed procedures Exporting the file to multiple cooling units. T Event and its error messages Upload Event and Error MessagesErrors generated by overridden values Event text DescriptionFile Transfers How to Upgrade FirmwareBenefits of upgrading firmware Firmware filesFirmware file transfer methods \cd\apc Use FTP or SCP to upgrade one cooling unitFtp open 150.250.6.10 Ftp put apchw03aosxxx.binUse Xmodem to upgrade one cooling unit Upgrade multiple cooling unitsInRow RC/RD/RP 600 mm User’s Guide Verifying Upgrades and Updates Last transfer result codesCode Description Page Page 2009 990-2937A