APC ACRC501 Service intervals, Air Filter-18 weeks Humidifier-26 weeks, Condensate Pump-52 weeks

Page 30

Service intervals

Set the service interval for each of the components, in weeks. The default are:

Air Filter—18 weeks

Humidifier—26 weeks

Heater—52 weeks

Condensate Pump—52 weeks

Fans—52 weeks

Compressor (ACRD500 series and ACRP100 series only)—52 weeks

Enable or disable alarm generation for the service intervals for each of the unit components, then click Apply to save your changes.

Thresholds

For ACRC500 and ACRP500 cooling units, configure high temperature thresholds for the rack inlet, supply air, return air, and entering fluid temperature sensors. Valid values are 0° to 37.2°C (32° to 99°F) for the entering fluid temperature sensors, and 0° to 100°C (32° to 212°F) for the rack inlet, supply air, and return air sensors.

For ACRP100 and ACRP500 cooling units, configure thresholds for supply high humidity and supply low humidity. Valid values are 0% to 100% relative humidity.

Click Apply to save your changes.

Sensor Values:

Rack Inlet Temperature — 68.5°F

Supply Air Temperature — 68.7°F

Return Air Temperature — 69.2°F

Supply Humidity — 29.3% RH

Return Humidity — 32.4% RDH

Thresholds:

Rack Inlet High Temperature — 32.0 - 212.0 °F

Supply Air Temperature — 32.0 - 212.0 °F

Return Air Temperature — 32.0 - 212.0 °F

Supply Humidity — 35.0 - 90.0 % RH

Return Humidity — 20.0 - 50.0 % RDH

22

InRow RC/RD/RP (600 mm) User’s Guide

Image 30 Contents
User’s Guide Page Contents Web Interface Administration Security Administration Notification Verifying Upgrades and Updates Page Introduction Features of the InRow RC/RD/RP 600 mm cooling unitInitial setup Product DescriptionInternal Management Features Access priority for logging onOverview Types of user accounts How to Recover from a Lost Password Watchdog Features Display Interface LEDsHow to Log On Remote access to the control consoleControl Console Local access to the control console Main Screen Example main screenInformation and status fields Main screen status fields Main menu Control Console MenusMenu structure Device Manager optionControl Administrator and Device Manager access Network optionSystem option Web Interface Supported Web browsersURL address formats Common browser error messages at log on Error Message Browser Cause of the ErrorQuick status SummaryNavigation tabs HelpSelect a tab to perform a task InRow RC/RD/RP 600 mm User’s Guide Home Alarm statusCooling Unit Operation GroupConfiguration SetpointsDehumid Deadband 2.0-10.0% Unit Detailed statusCompressor drive status ACRD500 and ACRP100 cooling units IdentificationRun hours Condensate Pump-52 weeks Service intervalsAir Filter-18 weeks Humidifier-26 weeks ThresholdsConfiguration Log LogsEvents Reverse lookupData GraphingInterval Hours specified as Delay hours between Uploads RotationParameter Description Setting Definition SyslogServers Settings Test How to use FTP or SCP to retrieve the log files Queries Modbus requests and Snmp GETs Local Users Administration SecuritySetting user access Permission levelsAuthentication Remote UsersInRow RC/RD/RP 600 mm User’s Guide Configuring the Radius Server Summary of the configuration procedureInactivity Timeout Configuring a Radius server on UNIX, with shadow passwordsSupported Radius servers TCP/IP settings Administration NetworkTCP/IP and communication settings SettingConfiguration page1 DhcpBoot mode transition. Tag 2, Len 1, Data 1/2 Dhcp response optionsAPC cookie. Tag 1, Len 4, Data 1APC Port speed DNS AdminstrationNetworkDNSservers Query Type Selected Query Question to UseEnabled WebOption Description On this link to view the certificate’s contents StatusConsole AESIs loaded Snmp Option Description FTP server Related TopicsEvent Actions Administration NotificationConfiguring event actions Types of notificationInRow RC/RD/RP 600 mm User’s Guide InRow RC/RD/RP 600 mm User’s Guide Active, Automatic, Direct Notification Mail notificationSetting Description SmtpSnmp traps Administration General Options Information about the Cooling UnitDate & time Unit preference User configuration file iniReset the interface Action DefinitionSerial Modbus Quick linksAbout Use the Wizard to configure basic TCP/IP settings APC Device IP Configuration WizardCapabilities, Requirements, and Installation InstallationLaunch the Wizard Configure the basic TCP/IP settings remotelyUse the Wizard Select Remotely over the network, and click NextConfigure or reconfigure the TCP/IP settings locally Select Locally through the serial port, and click NextContents of the .ini file How to Export Configuration SettingsSummary of the procedure Retrieving and Exporting the .ini FileDetailed procedures Exporting the file to multiple cooling units. T Errors generated by overridden values Upload Event and Error MessagesEvent and its error messages Event text DescriptionBenefits of upgrading firmware How to Upgrade FirmwareFile Transfers Firmware filesFirmware file transfer methods Ftp open 150.250.6.10 Use FTP or SCP to upgrade one cooling unit\cd\apc Ftp put apchw03aosxxx.binUpgrade multiple cooling units Use Xmodem to upgrade one cooling unitInRow RC/RD/RP 600 mm User’s Guide Verifying Upgrades and Updates Last transfer result codesCode Description Page Page 990-2937A 2009