Programming Parameters
*For charge voltages, battery warnings and shut down voltages, and high battery temperature, the parameter is changed by entering the actual value like example 4.3.2.
NOTE:
Only for APC personnel and certified local APC personnel.
4.3.2 Programming example – change charge voltage to 446V*
Action |
|
| Display shows | |
1. Press | and | simultaneously to open | Key in password | |
: | ||||
|
| for password input | ||
|
|
|
2.Enter password xx xx xx by pressing
|
|
|
| Last selected | |
|
|
|
| parameter | |
3. | Press | or | until | Boost charge voltage | |
: 438 | |||||
|
|
|
| ||
4. | Press |
|
| Boost charge voltage | |
|
| : 446 | |||
5. | Press | to store |
| Data stored | |
|
| ||||
6. | Wait about 1 second |
| Boost charge voltage | ||
| : 446 | ||||
7. | Press | to exit |
| Normal operation | |
| load power XX% | ||||
|
|
|
|
**The other parameters are
selected by pressing the key as step 4 in example 4.3.3. - one or more times.
4.3.3Programming example - change to output isolation transformer present**
Action |
|
| Display shows |
1. Press | and | simultaneously to open | Key in password |
|
| for password input | : |
|
|
|
2.Enter password xx xx xx by pressing
|
|
|
| Last selected | |
|
|
|
| parameter | |
3. | Press | or | until | Isolation trafo output | |
: NO | |||||
|
|
|
| ||
|
|
|
| Isolation trafo output | |
4. | Press | for change | : YES | ||
5. | Press | to store |
| Data stored | |
|
| ||||
6. | Wait about 1 second |
| Isolation trafo output | ||
| : YES | ||||
|
|
|
| ||
7. | Press | to exit |
| Normal operation | |
| load power XX% | ||||
|
|
|
| ||
|
|
|
| 7OA0002 US rev. 04 |
User Guide Silcon DP300E Series 480V | 19 |