APC DP300E manual Programming example change charge voltage to

Page 19

Programming Parameters

*For charge voltages, battery warnings and shut down voltages, and high battery temperature, the parameter is changed by entering the actual value like example 4.3.2.

NOTE:

Only for APC personnel and certified local APC personnel.

4.3.2 Programming example – change charge voltage to 446V*

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

:

 

 

for password input

 

 

 

2.Enter password xx xx xx by pressing

 

 

 

 

Last selected

 

 

 

 

parameter

3.

Press

or

until

Boost charge voltage

: 438

 

 

 

 

4.

Press

 

 

Boost charge voltage

 

 

: 446

5.

Press

to store

 

Data stored

 

 

6.

Wait about 1 second

 

Boost charge voltage

 

: 446

7.

Press

to exit

 

Normal operation

 

load power XX%

 

 

 

 

**The other parameters are

selected by pressing the key as step 4 in example 4.3.3. - one or more times.

4.3.3Programming example - change to output isolation transformer present**

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

 

 

for password input

:

 

 

 

2.Enter password xx xx xx by pressing

 

 

 

 

Last selected

 

 

 

 

parameter

3.

Press

or

until

Isolation trafo output

: NO

 

 

 

 

 

 

 

 

Isolation trafo output

4.

Press

for change

: YES

5.

Press

to store

 

Data stored

 

 

6.

Wait about 1 second

 

Isolation trafo output

 

: YES

 

 

 

 

7.

Press

to exit

 

Normal operation

 

load power XX%

 

 

 

 

 

 

 

 

7OA0002 US rev. 04

User Guide Silcon DP300E Series 480V 240-320kVA

19

Image 19
Contents User Guide Silcon DP300E Series 480V 240-320kVA Silcon DP300E Series 480V 240-320kVA User GuideImportant Safety Instructions Table of Contents Display unit IntroductionIntroduction GeneralStop stand-by Stop Start and Operating the External Service Bypass PanelStart from stand-by Switching off Silcon DP3240E DP3320E Stop for complete power downDisplay shows Starting up Silcon DP3240E DP3320E Start from complete power downLamp indication on bypass panel Single Utility Dual UtilityBypassing the UPS Action Display showsAction Switching the system from external bypass into normalSingle Utility UPS operationBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersKeys used for programming Programming example switch to bypass operation326 Programming of system configuration parameters438 346Programming example change charge voltage to Installation of new batteries Programming of battery monitorProgramming guide Description of settingsParallel programming/operation Programming parameters for advanced parallel operationProgramming example Highest Station No Alarm texts conc. parallel operation Parallel operation alarms GeneralOther reasons for parallel operation alarm Reading Out Measurements MeasurementsDescription Alarm messages AlarmsAlarms What To Do Alarm stackEvents logger Mode CommentsDisplaying the events stack Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Operation Possible alarm DescriptionRemote Display Remote DisplayAdjusting contrast Fan Preventive MaintenancePreventive Maintenance BatteryActions Display shows Battery capacity testMonitor function Battery monitor testFunctionality of battery test Back-up timeBattery monitor auto Operation of the battery monitorBattery monitor test Battery monitor resetEconomy Operation Economy OperationInput System SpecificationsSystem Specifications Technical dataHow to Contact APC How to Contact APC