Preventive Maintenance

8.0Preventive Maintenance

8.1General

The maintenance of the Silcon DP300E UPS systems should be carried out by trained service engineers. We recommend that you obtain a service and mainte- nance contract from APC or an APC certified and approved provider.

8.2Fan

It is recommended to replace the fans. Please contact your local APC dealer for replacement interval.

8.3Battery

8.3.1Control of batteries

The batteries can be controlled in two ways:

1.Battery capacity test

2.Battery monitor test

For safety reasons battery tests should preferably be made during uncritical periods for the loads connected.

8.3.2Function of battery capacity test

When performing a battery capacity test, the system switches to battery operation until low DC warning appears. The back-up time is valid for the actual load on the UPS, however, if load changes, the actual back-up time will change too. Then the UPS system will switch back to normal operation and back-up time will be stored in the battery capacity menu, see also section 8.4 on how to perform the test.

8.3.3Function of battery monitor test

When performing an automatic or a manual battery monitor test, the back-up time is shown in the display and the condition of the battery is checked. The back-up time is valid for the actual load on the UPS, however, if load changes, the actual back-up time will change too.

See also section 8.5 “Battery monitor test” for more information and how to perform the test. The result is one of the following:

1.Battery is OK – nothing will happen. Normal back-up time is OK.

2.Battery has reduced capacity – “Battery weak” is given. Reduced back-up time.

3.Battery capacity far to low – “Battery defective” is given. Limited to no back-up time.

7OA0002 US rev. 04

32

User Guide Silcon DP300E Series 480V 240-320kVA

Image 32
Contents Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStart from stand-by Stop Start and Operating the External Service Bypass PanelStop stand-by Display shows Stop for complete power downSwitching off Silcon DP3240E DP3320E Start from complete power down Starting up Silcon DP3240E DP3320ESingle Utility Dual Utility Bypassing the UPSAction Display shows Lamp indication on bypass panelSwitching the system from external bypass into normal Single UtilityUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Keyboard description OperationOperation Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programmingProgramming of system configuration parameters 438346 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesDescription of settings Parallel programming/operationProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Other reasons for parallel operation alarm Parallel operation alarms GeneralAlarm texts conc. parallel operation Description MeasurementsReading Out Measurements Alarms Alarms What To DoAlarm stack Alarm messagesDisplaying the events stack Mode CommentsEvents logger Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Possible alarm Description Remote DisplayRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanBattery capacity test Actions Display showsBattery monitor test Functionality of battery testBack-up time Monitor functionOperation of the battery monitor Battery monitor testBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC