APC DP300E manual Single Utility Dual Utility, Bypassing the UPS, Action Display shows

Page 8

Stop, Start & Operating the External Service Bypass Panel

Single Utility

Dual Utility

2.6Operating the external service bypass switch, single systems

2.6.1Bypassing the UPS

Action

 

 

Display shows

1.

Press

on the keyboard

 

2.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

4.

Press

on the keyboard

 

Lamp indication on bypass panel

WARNING!

If the UPS is out of service for more than 48 hours the connected batteries might be damaged. Refer to total “Switching off“ as described in

5.Check lamp indication on the bypass panel

6.Turn the external bypass switch (Q003) to position “1“.

7.Turn the output switch (Q002) to position “0“.

8.Open the front door and press the red “OFF“ push-button.

The acoustic alarm sounds for 30 secs.*

9.Turn the input switch (Q001) to position “0“. Turn the bypass input switch (Q010) to position “0”, if dual utility is present.

The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs.

The green lamp (H003) above the bypass switch handle (Q003) lights

The green lamp (H002) above the output switch handle (Q002) lights

Only the lamp (H002) above the output switch handle (Q002) lights now

Display shows

**System OFF**

chapter 2.4.1.

7OA0002 US rev. 04

* The acoustic alarm can be reset by the key

EMERGENCY (UPS not alive)

1.Turn the bypass switch (Q003) to position “1“.

2.Turn the output switch (Q002) to position “0“.

3.Turn the input switch (Q001) to position “0“.

4.If dual utility is present, turn bypass input switch (Q010) to position “0”.

5.Change released system input fuse(s), if any.

8

User Guide Silcon DP300E Series 480V 240-320kVA

Image 8
Contents Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStart from stand-by Stop Start and Operating the External Service Bypass PanelStop stand-by Display shows Stop for complete power downSwitching off Silcon DP3240E DP3320E Start from complete power down Starting up Silcon DP3240E DP3320ESingle Utility Dual Utility Bypassing the UPSAction Display shows Lamp indication on bypass panelSwitching the system from external bypass into normal Single UtilityUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Keyboard description OperationOperation Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programmingProgramming of system configuration parameters 438346 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesDescription of settings Parallel programming/operationProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Other reasons for parallel operation alarm Parallel operation alarms GeneralAlarm texts conc. parallel operation Description MeasurementsReading Out Measurements Alarms Alarms What To DoAlarm stack Alarm messagesDisplaying the events stack Mode CommentsEvents logger Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Possible alarm Description Remote DisplayRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanBattery capacity test Actions Display showsBattery monitor test Functionality of battery testBack-up time Monitor functionOperation of the battery monitor Battery monitor testBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC