APC DP300E manual Reading Out Measurements, Description

Page 24

Measurements

5.0Reading Out Measurements

Press as indicated below one key or two keys simultaneously (values used are only random for illustration):

NOTE:

Utility = Mains

7OA0002 US rev. 04

Action

Display shows

98.01.16

10.22,13

Mains 1 voltage 480 480 480 Vac

Mains 1 Current

100 100 100 Aac

Mains 2 voltage 480 480 480 Vac

Mains 2 Current

100 100 100 Aac

Battery voltage

438 437 Vdc

Battery current

+ 20 Adc

Output voltage

480 480 480 Vac

Output current

180 180 180 Aac

Output frequency

60Hz

Battery temp.

25ºC

Output peak current

255 255 255 A

Normal operation load power xx%

Batt. load : 0

Batt. tank : 100

Description

Year, month, day

Hour, minute, second

Utility 1 voltage is 3 x 480 Vac

Utility 1 current is 3 x 100 Aac

Utility 2 voltage is 3 x 480 Vac

Utility 2 current is 3 x 100 Aac

Battery voltage is 438 Vdc on batt.1. 437 Vdc on batt.2.

Charging current is (+) 20 Adc (Discharging current ())

Output voltage is 3 x 480 Vac

Output current is 3 x 180 Aac

Output frequency is 60 Hz

Battery temperature is 25°C (77°F)

Output peak current is 3 x 255 A

Returns to normal status indication. If not pressed, automatic switch back will be performed after 20 seconds.

Battery load in procent.

Left battery capacity in procent.

24

User Guide Silcon DP300E Series 480V 240-320kVA

Image 24
Contents Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop Start and Operating the External Service Bypass Panel Stop stand-byStart from stand-by Stop for complete power down Switching off Silcon DP3240E DP3320EDisplay shows Start from complete power down Starting up Silcon DP3240E DP3320ESingle Utility Dual Utility Bypassing the UPSAction Display shows Lamp indication on bypass panelSwitching the system from external bypass into normal Single UtilityUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programmingProgramming of system configuration parameters 438346 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesDescription of settings Parallel programming/operationProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Parallel operation alarms General Alarm texts conc. parallel operationOther reasons for parallel operation alarm Measurements Reading Out MeasurementsDescription Alarms Alarms What To DoAlarm stack Alarm messagesMode Comments Events loggerDisplaying the events stack Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Possible alarm Description Remote DisplayRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanBattery capacity test Actions Display showsBattery monitor test Functionality of battery testBack-up time Monitor functionOperation of the battery monitor Battery monitor testBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC