APC DP300E manual Programming of battery monitor, Installation of new batteries

Page 20

Programming Parameters

NOTE:

Only for APC personnel and certified local APC personnel.

4.4Programming of battery monitor

Action

 

 

Display shows

1. Press

and

simultaneously to open

Key in password

 

 

for password input

:

 

 

 

2.Enter password xx xx xx by pressing

Last selected

parameter

3. Press

or

until

Expected back-up

time [min.]: XXX.X

 

 

 

4.Enter the expected back-up time in min. at 100% ohmic (pf = 1) load, when the inverter has a mean efficiency of approx. 96%

Press I.e. 14.0 min.

5.Press to store data

6. Press or until

7 Press

to set Ah for battery

8.Press to store data

9.Press to exit

Expected back-up

time [min.]: 14.0

Data stored

Battery capacity

in [Ah]: XX.X

Battery capacity

in [Ah]: 7.0

Data stored

Normal operation load power XX%

Installation of new batteries:

When installing new batteries the procedure in section 4.4 MUST be carried out, otherwise the monitor may give false alarms.

7OA0002 US rev. 04

20

User Guide Silcon DP300E Series 480V 240-320kVA

Image 20
Contents Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStart from stand-by Stop Start and Operating the External Service Bypass PanelStop stand-by Display shows Stop for complete power downSwitching off Silcon DP3240E DP3320E Start from complete power down Starting up Silcon DP3240E DP3320ESingle Utility Dual Utility Bypassing the UPSAction Display shows Lamp indication on bypass panelSwitching the system from external bypass into normal Single UtilityUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Keyboard description OperationOperation Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programmingProgramming of system configuration parameters 438346 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesDescription of settings Parallel programming/operationProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Other reasons for parallel operation alarm Parallel operation alarms GeneralAlarm texts conc. parallel operation Description MeasurementsReading Out Measurements Alarms Alarms What To DoAlarm stack Alarm messagesDisplaying the events stack Mode CommentsEvents logger Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Possible alarm Description Remote DisplayRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanBattery capacity test Actions Display showsBattery monitor test Functionality of battery testBack-up time Monitor functionOperation of the battery monitor Battery monitor testBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC