APC DP300E manual Isolating one UPS for service/maintenance

Page 14

Stop, Start & Operating the External Service Bypass Panel

Single Utility

2.5.3 Isolating one UPS for service/maintenance

H003

Utility

Q003

Service bypass switch

H002b

H004

Q004

H002a

In a redundant system one UPS can be isolated for service/maintenance without

Load

affecting the other parallel UPS(s).

 

 

1. Check that the remaining UPS(s) will be able to carry the load when one UPS is

 

isolated.

Q001a

Q001b

Q002b

 

 

DP300E

Q002a

2.Switch off the system to be isolated for maintenance by pushing the red “OFF” push-button.

3.Disconnect output and utility by turning output switch (Q002) to position “0” and input switch (Q001) to position “0”, disconnect battery by opening battery MCCB.

DP300E

If dual utility is present, turn the bypass input switch (Q010) to position “0”.

Dual Utility

 

H003

 

Utility 2

 

Load

 

Q003

 

Service bypass switch

H004

 

Q004

 

H010a

 

 

Q010a

H002a

 

 

 

Utility 1

DP300E

 

Q001a

Q002a

 

H010b

 

 

Q010b

H002b

 

 

DP300E

 

Q001b

Q002b

 

Switching back the UPS to normal parallel/redundant operation

1.Turn the input switch (Q001) and the output switch (Q002) to position “1”. If dual utility is present, turn the bypass input switch (Q010) to position “1”.

2.Charge capacitors, connect battery and start up the UPS as described in chapter 2.5.

The UPS will automatically switch to normal operation and start load sharing with the other parallelled UPS(s).

WARNING!

The system will discharge built- in capacitors. However, before working on the system check with a multimeter that there is no dangerous voltage on the terminals.

NOTE:

When Q002 is in position “0” the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if proper monitoring has been installed. Available on all APC bypass panels.

7OA0002 US rev. 04

14

User Guide Silcon DP300E Series 480V 240-320kVA

Image 14 Contents
Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents General IntroductionIntroduction Display unitStart from stand-by Stop Start and Operating the External Service Bypass PanelStop stand-by Display shows Stop for complete power downSwitching off Silcon DP3240E DP3320E Start from complete power down Starting up Silcon DP3240E DP3320EAction Display shows Single Utility Dual UtilityBypassing the UPS Lamp indication on bypass panelUPS operation Switching the system from external bypass into normalSingle Utility Action Bypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Keyboard description OperationOperation Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programming346 Programming of system configuration parameters438 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesProgramming parameters for advanced parallel operation Description of settingsParallel programming/operation Programming guideProgramming example Highest Station No Other reasons for parallel operation alarm Parallel operation alarms GeneralAlarm texts conc. parallel operation Description MeasurementsReading Out Measurements Alarm stack AlarmsAlarms What To Do Alarm messagesDisplaying the events stack Mode CommentsEvents logger Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Battery Preventive MaintenancePreventive Maintenance FanBattery capacity test Actions Display showsBack-up time Battery monitor testFunctionality of battery test Monitor functionBattery monitor reset Operation of the battery monitorBattery monitor test Battery monitor autoEconomy Operation Economy OperationTechnical data System SpecificationsSystem Specifications InputHow to Contact APC How to Contact APC