Stop, Start & Operating the External Service Bypass Panel
WARNING!
Please read chapter 2.4.1 “Switching off” in this User Guide, if UPS has to be stopped for more than 48 hours.
2.0Stop – Start and Operating the External Service Bypass Panel
2.1General
CAUTION!
To avoid possible personal injury or equipment damage, be aware that there may be AC voltage at the UPS’s output terminals/receptacles any time AC input power or DC battery voltage is applied. The UPS can provide output voltage from the batteries even when there is no AC input line voltage. When AC voltage is present, the UPS can provide output voltage even when the batteries are disconnected. If you want to be certain that there is no UPS output voltage, always disconnect the AC input source, switch off the UPS, AND switch off the DC. TEST BEFORE TOUCHING!
Some units have been programmed at the factory for autostart. When this para- meter is programmed to be on, the unit will automatically switch on whenever utility (AC line) is applied. To switch this parameter off, see chapter 4.0.
For safety reasons, only qualified service personnel should do a complete
Although users cannot completely
WARNING!
If the UPS system is installed with a service bypass panel, and the load equipment must remain energized from utility, refer to operating service bypass panel before proceeding chapter 2.2 - 2.5.
2.2Stop (stand-by)
Action | Display shows | Description |
Open the front door | System off | Alarm LED lights. Acoustic |
and activate the red | ||
“OFF” |
| alarm sounds for 30 seconds. |
|
|
|
2.3Start (from stand-by)
Action | Display shows | |
Open the front door and | Normal operation | |
activate the green “ON” | ||
Load power xx% | ||
| ||
|
|
7OA0002 US rev. 04
User Guide Silcon DP300E Series 480V | 5 |