APC DP300E manual System Specifications, Technical data, Input, Output

Page 37

System Specifications

10.0System Specifications

10.1Technical data

Input

Voltage

3 x 480V

 

 

 

 

Voltage tolerance

 

 

Normal operation

±15%

 

Bypass operation

±10% (standard)

 

 

±4, 6, 8% (programmable)

 

 

 

 

Frequency

60Hz

 

 

±6% standard

 

 

±0,5-8% (programmable)

 

 

 

 

Input PF

Load 25% min. 0,97

 

 

Load 100% min. 0,99

 

 

 

 

Current distortion

Max. 5%

 

 

 

Output

Voltage

3 x 480V

 

 

 

 

Voltage tolerance

±1% static, sym. load

 

 

±3% static, asym. load

 

 

±5% 0-100% load step

 

 

 

 

Voltage distortion

Max. 3%, linear load

 

 

Max. 5%, non-linear load

 

 

(Silcon DP3240E-DP3320E)

 

 

 

 

Load power factor

0,9 lead to 0,8 lag

 

 

 

 

Frequency

60Hz (utility synchronized)

 

 

±0,1% free running

 

 

 

 

Overload capacity

 

 

Normal operation

200% - 60 secs.

 

Normal operation

125% - 10 min.

 

Battery operation

150% - 30 secs.

 

Bypass operation

125% - cont.

 

 

 

General

Ambient temperature

0-40°C/32-104°F

 

 

(Above 25°C/77°F the battery life

 

 

time is reduced)

 

 

 

 

Humidity

Max. 95%, non condensing

 

Protection class

NEMA 1

 

Safety

EN50091-1

 

 

UL 1778

 

Emission and Immunity

EN50091-2

 

Static bypass switch

Built-in

 

Auto restart

Programmable

 

Economy mode

Programmable

 

 

 

7OA0002 US rev. 04

User Guide Silcon DP300E Series 480V 240-320kVA

37

Image 37
Contents User Guide Silcon DP300E Series 480V 240-320kVA Silcon DP300E Series 480V 240-320kVA User GuideImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop stand-by Stop Start and Operating the External Service Bypass PanelStart from stand-by Switching off Silcon DP3240E DP3320E Stop for complete power downDisplay shows Starting up Silcon DP3240E DP3320E Start from complete power downBypassing the UPS Single Utility Dual UtilityAction Display shows Lamp indication on bypass panelSingle Utility Switching the system from external bypass into normalUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersKeys used for programming Programming example switch to bypass operation438 Programming of system configuration parameters346 326Programming example change charge voltage to Installation of new batteries Programming of battery monitorParallel programming/operation Description of settingsProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Alarm texts conc. parallel operation Parallel operation alarms GeneralOther reasons for parallel operation alarm Reading Out Measurements MeasurementsDescription Alarms What To Do AlarmsAlarm stack Alarm messagesEvents logger Mode CommentsDisplaying the events stack Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanActions Display shows Battery capacity testFunctionality of battery test Battery monitor testBack-up time Monitor functionBattery monitor test Operation of the battery monitorBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC