APC DP300E Parallel programming/operation, Programming parameters for advanced parallel operation

Page 21

Programming Parameters

NOTE:

Common battery pack is a technical possibility. However, APC recommend separate battery pack due to a higher safety degree in con- nection with redundant/parallel operation.

The UPS system is prepared for both solutions.

4.5Parallel programming/operation

Programming parameters for advanced parallel operation

To use the advanced parallel functions the following parameters must be pro- grammed:

1.“Station number”

2.“Highest station address”

3.“Advanced power management”

4.“APM test mode active”

5.“Battery connection”

Description of settings.

1.“Station number”

Valid station numbers: 1-9 stating the UPS parallel address in the system.

2.“Highest station number”

Valid station numbers: 2-9 stating the number of UPS’s in the system.

3.“Advanced power management”

“Disabled”: Advanced power management is inactive.

“PARALLEL+1”: Advanced power management is activated when the system operates as PARALLEL+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPS).

“REDUNDANT+1”: Advanced power management is activated when the system operates as REDUNDANT+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPS) with one spare system.

4.“APM test mode active”

“No”: Stand-by time will be 24 hours - on-line time will be 48 hours * N systems.

“Yes”: Stand-by time will be 1 min. - on-line time will be 2 min. * N systems.

5.“Battery connection”

“Separate”: Separate battery for this UPS.

“Common”: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems is used (for charge voltage compensating).

Programming guide.

Example with 3 systems in parallel with separate batteries.

Programme the station addresses 1-3: 1 for UPS 1, 2 for UPS 2 and 3 for UPS 3

All UPS systems have to be programmed to “Highest station address” = 3.

If APM should not be tested, “APM test mode active” must be “NO”.

If a system is isolated due to service the station numbers must be reprogrammed for the remaining active systems starting with number 1 and ending with max. number of active systems. No numbers must be left out in this sequence. Fur- thermore “Highest station address” must be changed to number of active UPS’s in parallel.

7OA0002 US rev. 04

User Guide Silcon DP300E Series 480V 240-320kVA

21

Image 21 Contents
User Guide Silcon DP300E Series 480V 240-320kVA Silcon DP300E Series 480V 240-320kVA User GuideImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop Start and Operating the External Service Bypass Panel Stop stand-byStart from stand-by Stop for complete power down Switching off Silcon DP3240E DP3320EDisplay shows Starting up Silcon DP3240E DP3320E Start from complete power downBypassing the UPS Single Utility Dual UtilityAction Display shows Lamp indication on bypass panelSingle Utility Switching the system from external bypass into normalUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Programming Parameters Parameter Setting CommentsProgramming Parameters Parameters Keys used for programming Programming example switch to bypass operation438 Programming of system configuration parameters346 326Programming example change charge voltage to Installation of new batteries Programming of battery monitorParallel programming/operation Description of settingsProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Parallel operation alarms General Alarm texts conc. parallel operationOther reasons for parallel operation alarm Measurements Reading Out MeasurementsDescription Alarms What To Do AlarmsAlarm stack Alarm messagesMode Comments Events loggerDisplaying the events stack Possible alarm Description Action Possible alarmsTemperature on static bypass System is locked in oper UPS has attempted 10 times Remote Display Possible alarm DescriptionRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanActions Display shows Battery capacity testFunctionality of battery test Battery monitor testBack-up time Monitor functionBattery monitor test Operation of the battery monitorBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC