APC DP300E manual Economy Operation

Page 36

Economy Operation

NOTE:

When using economy mode there is NO power factor correction on the input or regulation of output voltage.

9.0Economy Operation

9.1General

In economy operation the load is supplied directly from the utility, however the UPS is monitoring the utility and the output voltages and will in case of utility failure switch to battery operation without interruptions.

The system will in order to keep the batteries fully charged at all times switch to normal operation in a pre-programmed time sequence.

The operation of the system is the same as already described in this guide with the exception of the following points:

-When starting up, the system will at first go into normal operation to ensure a fully charged battery, but will then switch into bypass after the programmed time (8-10 hours).

7OA0002 US rev. 04

36

User Guide Silcon DP300E Series 480V 240-320kVA

Image 36
Contents Silcon DP300E Series 480V 240-320kVA User Guide User Guide Silcon DP300E Series 480V 240-320kVAImportant Safety Instructions Table of Contents Introduction IntroductionGeneral Display unitStop Start and Operating the External Service Bypass Panel Stop stand-byStart from stand-by Stop for complete power down Switching off Silcon DP3240E DP3320EDisplay shows Start from complete power down Starting up Silcon DP3240E DP3320ESingle Utility Dual Utility Bypassing the UPSAction Display shows Lamp indication on bypass panelSwitching the system from external bypass into normal Single UtilityUPS operation ActionBypassing the parallel UPS system Emergency UPS not alive Press on the keyboard Press or on the keyboard until Following can be carried out on any UPS Isolating one UPS for service/maintenance Operation OperationKeyboard description Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming example switch to bypass operation Keys used for programmingProgramming of system configuration parameters 438346 326Programming example change charge voltage to Programming of battery monitor Installation of new batteriesDescription of settings Parallel programming/operationProgramming parameters for advanced parallel operation Programming guideProgramming example Highest Station No Parallel operation alarms General Alarm texts conc. parallel operationOther reasons for parallel operation alarm Measurements Reading Out MeasurementsDescription Alarms Alarms What To DoAlarm stack Alarm messagesMode Comments Events loggerDisplaying the events stack Possible alarms Possible alarm Description ActionTemperature on static bypass System is locked in oper UPS has attempted 10 times Possible alarm Description Remote DisplayRemote Display Remote Display OperationAdjusting contrast Preventive Maintenance Preventive MaintenanceBattery FanBattery capacity test Actions Display showsBattery monitor test Functionality of battery testBack-up time Monitor functionOperation of the battery monitor Battery monitor testBattery monitor reset Battery monitor autoEconomy Operation Economy OperationSystem Specifications System SpecificationsTechnical data InputHow to Contact APC How to Contact APC