External Connection
4.4.1 Relay Board/Relay Functions
NOTICE
If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure
Relay Number | Message |
| |
|
|
| |
1 ## (X002) | Mains outside limits | Mains voltage RMS outside limits | |
|
|
| Mains wave form (fast detector) outside limits |
|
|
| Mains frequency outside limits |
|
|
| |
2 ## (X003) | Bypass outside limits | Bypass voltage RMS outside limits | |
|
|
| Bypass wave form (fast detector) outside limits |
|
|
| Bypass frequency outside limits |
|
|
|
|
3 ## | (X004) | Output outside limits | Output voltage RMS value outside limits |
|
|
| Output wave form (fast detector) outside limits |
|
|
| Output frequency outside limits |
|
|
|
|
4 | (X005) | System overload | Output load exceeding 100% |
|
|
| Delta inverter current limiter active |
|
|
| Main inverter current limiter active |
|
|
|
|
5 | (X006) | Fan fault | Blocked or faulty fan |
|
|
|
|
6 | (X007) | High Equipment | Static switch temperature too high |
|
| Temperature or | Main inverter failure (temperature too high or fuse blown) |
|
| Inverter Fuse Blown | Delta inverter temperature too high |
|
|
| Magnetic temperature too high |
|
|
| Isolation transformer (option) temperature too high |
|
|
| Battery temperature too high |
|
|
|
|
7 | (X008) | MCCB battery off | Battery MCCB/Fuse not closed or released |
|
|
|
|
8 | (X009) | Normal operation | UPS running in normal operation mode |
|
|
| (status) |
|
|
| |
9 ## (X010) | Battery operation | UPS running in battery operation mode | |
|
|
| (status) |
|
|
| |
10 ## (X011) | Bypass operation | UPS running in bypass operation mode | |
|
|
| (status) |
|
|
| |
11 ## (X012) | UPS in | ||
|
|
| (Hot |
|
|
|
|
12 | (X013) | Service bypass | Service bypass switch active |
|
| operation |
|
|
|
| |
13 ## (X014) | Boost charge | UPS | |
|
| operation |
|
|
|
|
|
14 | (X015) | Battery voltage | DC voltage too high (shut down) |
|
| outside limits | DC voltage below warning level |
|
|
| DC voltage too low (shut down) |
|
|
|
|
15 | (X016) | Battery condition | ABM has detected weak battery condition |
|
| fault | ABM has detected defect battery |
|
|
| (ABM = Advanced Battery Monitor) |
|
|
| |
16 ## (X017) | Common fault | All alarms as mentioned above | |
|
|
| (except relays 8+9+10+11) |
|
|
| Internal power supply fault |
|
|
| System locked in operation mode |
|
|
| Internal memory fault |
|
|
| Internal communication fault |
|
|
|
|
##Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds.
| |
|
|
Installation Guide APC Silcon 480kW 400V UPS | 15 |