External Connection
4.4.1 Relay Board/Relay Functions
NOTICE
If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure
| Relay Number | Message | 
 | |
| 
 | 
 | 
 | |
| 1 ## (X002) | Mains outside limits | Mains voltage RMS outside limits | |
| 
 | 
 | 
 | Mains wave form (fast detector) outside limits | 
| 
 | 
 | 
 | Mains frequency outside limits | 
| 
 | 
 | 
 | |
| 2 ## (X003) | Bypass outside limits | Bypass voltage RMS outside limits | |
| 
 | 
 | 
 | Bypass wave form (fast detector) outside limits | 
| 
 | 
 | 
 | Bypass frequency outside limits | 
| 
 | 
 | 
 | 
 | 
| 3 ## | (X004) | Output outside limits | Output voltage RMS value outside limits | 
| 
 | 
 | 
 | Output wave form (fast detector) outside limits | 
| 
 | 
 | 
 | Output frequency outside limits | 
| 
 | 
 | 
 | 
 | 
| 4 | (X005) | System overload | Output load exceeding 100% | 
| 
 | 
 | 
 | Delta inverter current limiter active | 
| 
 | 
 | 
 | Main inverter current limiter active | 
| 
 | 
 | 
 | 
 | 
| 5 | (X006) | Fan fault | Blocked or faulty fan | 
| 
 | 
 | 
 | 
 | 
| 6 | (X007) | High Equipment | Static switch temperature too high | 
| 
 | 
 | Temperature or | Main inverter failure (temperature too high or fuse blown) | 
| 
 | 
 | Inverter Fuse Blown | Delta inverter temperature too high | 
| 
 | 
 | 
 | Magnetic temperature too high | 
| 
 | 
 | 
 | Isolation transformer (option) temperature too high | 
| 
 | 
 | 
 | Battery temperature too high | 
| 
 | 
 | 
 | 
 | 
| 7 | (X008) | MCCB battery off | Battery MCCB/Fuse not closed or released | 
| 
 | 
 | 
 | 
 | 
| 8 | (X009) | Normal operation | UPS running in normal operation mode | 
| 
 | 
 | 
 | (status) | 
| 
 | 
 | 
 | |
| 9 ## (X010) | Battery operation | UPS running in battery operation mode | |
| 
 | 
 | 
 | (status) | 
| 
 | 
 | 
 | |
| 10 ## (X011) | Bypass operation | UPS running in bypass operation mode | |
| 
 | 
 | 
 | (status) | 
| 
 | 
 | 
 | |
| 11 ## (X012) | UPS in  | ||
| 
 | 
 | 
 | (Hot  | 
| 
 | 
 | 
 | 
 | 
| 12 | (X013) | Service bypass | Service bypass switch active | 
| 
 | 
 | operation | 
 | 
| 
 | 
 | 
 | |
| 13 ## (X014) | Boost charge | UPS  | |
| 
 | 
 | operation | 
 | 
| 
 | 
 | 
 | 
 | 
| 14 | (X015) | Battery voltage | DC voltage too high (shut down) | 
| 
 | 
 | outside limits | DC voltage below warning level | 
| 
 | 
 | 
 | DC voltage too low (shut down) | 
| 
 | 
 | 
 | 
 | 
| 15 | (X016) | Battery condition | ABM has detected weak battery condition | 
| 
 | 
 | fault | ABM has detected defect battery | 
| 
 | 
 | 
 | (ABM = Advanced Battery Monitor) | 
| 
 | 
 | 
 | |
| 16 ## (X017) | Common fault | All alarms as mentioned above | |
| 
 | 
 | 
 | (except relays 8+9+10+11) | 
| 
 | 
 | 
 | Internal power supply fault | 
| 
 | 
 | 
 | System locked in operation mode | 
| 
 | 
 | 
 | Internal memory fault | 
| 
 | 
 | 
 | Internal communication fault | 
| 
 | 
 | 
 | 
 | 
##Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds.
| 
 | |
| 
 | 
 | 
| Installation Guide APC Silcon 480kW 400V UPS | 15 |